Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

Fieldbus Surge Protector, Field Mounting (Ex ia) F*-LBF-I1.32

F*-LBF-I1.32
  • Surge Protector in stainless steel housing
  • Intrinsically safe, FISCO or Entity
  • Surge protection for '+' and '-' fieldbus lead
  • Choice of threads 20 mm or 1/2" NPT
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  F*-LBF-I1.32

General specifications
Design / MountingOutside installation
Electrical specifications
Rated voltage32 V
Rated current550 mA
Nominal discharge current (8/20 µs)
per line10 kA
total10 kA
Max. surge current (8/20 µs)10 kA
Voltage protection level at max. rated current
Line/Line58 V
Line/Earth1700 V
Voltage protection level at 1 kV/µsec
Line/Line50 V
Line/Earth1.2 kV
Reaction time
Line/Linemax. 1 ns
Line/Earthmax. 100 ns
Capacitance
Line/Line25 pF
Line/Earth15 pF
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2
Surge protectionIEC 61643-21
Ambient conditions
Ambient temperature-50 ... 80 °C (-58 ... 176 °F)
Storage temperature-50 ... 85 °C (-58 ... 185 °F)
Mechanical specifications
Core cross section1.3 mm2
Housing materialStainless steel 1.4401 (AISI 316)
surface all over polished
Degree of protectionIP00/IP67 if correctly installed
Mass160 g
Mountingscrew mounting
Data for application in connection with hazardous areas
EU-type examination certificateKEMA 04 ATEX 1317 X
MarkingEx-Hexagon II 2(1)G Ex ia IIC T6...T4
VoltageEntity 30 V , FISCO 17.5 V
CurrentEntity 550 mA , FISCO 380 mA
PowerEntity 3 W , FISCO 5.32 W
Internal capacitancenegligible 0 nF
Internal inductancenegligible 0 µH
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 , EN 60079-11:2012
International approvals
IECEx approvalIECEx KEM 09.0081X
Approved forEx ia [ia Ga] IIC T6...T4 Gb
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.019170104
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC001604
UNSPSC 12.139121610

Details: F*-LBF-I1.32

Informative Literature: F*-LBF-I1.32

Seleccionar idioma:
LiteratureIdiomaTipo de archivoTamaño
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F*-LBF-I1.32

Seleccionar idioma:
Safety and Security DocumentationIdiomaTipo de archivoTamaño
Manual de instruccionesSPAPDF152 KB
Manuals
ManualENGPDF232 KB

Design / Simulation: F*-LBF-I1.32

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
CAD 3-D / CAD 3-DALLSTP102 KB

Approvals: F*-LBF-I1.32

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
China CNEX CCC Ex Certificate2021312304001165 (Germany)ALLPDF1038 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe KEMAKEMA 04 ATEX 1317XALLPDF1647 KB
KEMA IECEx Certificate of ConformityIECEx KEM 09.0081XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0511CSPASPAPDF1138 KB

Ethernet-APL permite una comunicación continua en todos los niveles jerárquicos. Obtenga más información sobre esta tecnología pionera...

Servicio de información RSS para actualizaciones de PANOS

Manténgase informado cuando  se publique una nueva actualización de software de PANOS, el sistema operativo para conmutadores Ethernet-APL: Con nuestro canal RSS recibirá una notificación por correo electrónico en su bandeja de entrada inmediatamente después de que se haya publicado una nueva versión.

Desde las decisiones a la planificación, instalación y puesta en marcha, hasta el funcionamiento y mantenimiento: descubra cómo sacar el máximo partido de su infraestructura de bus de campo…