Cable Glands, Metal, for shielded EMC Cables CG.EM.*.*.*

CG.EM.*.*.*
  • For shielded EMC cables without armor
  • Brass nickel-plated or stainless steel
  • Metric and NPT versions available
  • Ex db, Ex eb and Ex tb certified
  • Suitable for operation in Zone 1, Zone 2, Zone 21 and Zone 22
  • Suitable for operation in Class I, Zone 1/2/22
  • Suitable for operation in Class I, Division 2 when installed in accordance with NEC501.10(B)(2)
  • Degree of protection IP66 / IP68, UL Type 4X

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Descargue la hoja de datos completa en PDF::


Extracto de la hoja de datos: Información técnica del  CG.EM.*.*.*

Mechanical specifications
Cable typenon-armored shielded EMC cables
Clamping range (D)see PDF data sheet
Thread typemetric ISO pitch 1.5 mm or NPT ANSI ASME B1.20.1
Thread size (TD)see PDF data sheet
Degree of protectionIP66 / IP68 , UL Type 4X
Material
Finishinherent color silver
Cable glandbrass nickel-plated or AISI 316 (1.4401) stainless steel
Washer gasketaramid fibers bonded with NBR
O-Ringchloroprene / neoprene or silicone
Seal insertchloroprene / neoprene or silicone
Masssee PDF data sheet
Dimensionssee PDF data sheet
Ambient conditions
Ambient temperatureEx eb and Ex tb versions:
chloroprene seal: -40 ... 80 °C (-40 ... 176 °F)
silicone seal: -60 ... 140 °C (-76 ... 284 °F)
washer gasket: -50 ... 80 °C (-58 ... 176 °F)
sealing plugs: -60 ... 70 °C (-76 ... 158 °F)
Ex db versions:
chloroprene seal: -40 ... 80 °C (-40 ... 176 °F)
silicone seal: -60 ... 80 °C (-76 ... 176 °F)
washer gasket: -50 ... 80 °C (-58 ... 176 °F)
Service temperature might be limited by the use of sealing plugs or washer gaskets.
Data for application in connection with hazardous areas
EU-type examination certificateIMQ 14 ATEX 012X
MarkingEx-Hexagon II 2 GD
Ex db IIC Gb
Ex eb IIC Gb
Ex tb IIIC Db
International approvals
UL approval
cULusE490962 tested to UL 2225
CSA approvalCSA 60079-7 , CSA 60079-31
IECEx approvalIECEx IMQ 14.0004X
EAC approvalTC RU C-TR.GB05.B.00918
Conformity
Degree of protectionEN 60529
CE marking0102
General information
Scope of deliveryK01 - metric variants, individual component: Cable gland , washer gasket , locknut , earth tag , shroud PVC , brief instructions
K01 - NPT variants, individual component: Cable gland , shroud PVC , brief instructions
Knn - packing unit with multiple components: Cable glands , brief instructions (1 copy)
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Accessories
Sealing plugssee PDF data sheet

Documents: CG.EM.*.*.*

Short instructions, safety informationIdiomaTipo de archivoTamaño
Brief Instructions Cable Glands Series CG.NA.*/CG.EM.*ENGPDF2826 KB
Kurzanleitung Kabelverschraubungen Serien CG.NA.*/CG.EM.*GERPDF2830 KB

Approvals+Certificates: CG.EM.*.*.*

Statements of complianceNúmero de CertificadoTipo de archivoTamaño
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-1897BPDF101 KB
Certificates
Brasil DNV GL BrasilDNV 20.0029 XPDF444 KB
Europe IMQ ATEX Category 2 D ATEX Category 2 GIMQ 14 ATEX 012 XPDF2921 KB
IMQ IECEx Certificate of ConformityIECEx IMQ 14.0004XLINK---
UL cULE490962LINK---
Guía de selección rápida para equipos de protección contra explosiones eléctricas

Consiga una copia en PDF gratis de nuestra guía de selección rápida para equipos de protección contra explosiones eléctricas. Ofrece una descripción completa de toda nuestra gama de productos.