Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Descargue la hoja de datos completa en PDF:
Extracto de la hoja de datos: Información técnica del
KLD2-PC-1.1.IEC
Supply |
Connection | Power Rail or terminals 8+, 11+; 9-, 12- |
Rated voltage | 16 ... 32 V DC |
Rated current | 1.02 A |
Power dissipation | 16 ... 32 V at 1 A: ≤ 1.86 W; typ. 1.6 W |
Fieldbus connection |
Field-side | |
| Connection | terminals 3+, 6+; 2-, 5-; 1S, 4S (S=screen connection) |
| Rated voltage | 14.7 ... 30.7 V DC |
| Rated current | 1 A |
| Terminating impedance | 100 Ω switchable off and on via rotary switch: 1 -> on; 0 -> off |
Error message output |
Connection | Power Rail or terminals 7, 10 |
Rated voltage | 32 V DC |
Rated current | 10 mA |
Voltage drop | 1.2 V at 10 mA |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Standard conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC/EN 60529 |
Fieldbus standard | IEC 61158-2, ISA S 50.02 part 2 |
Climatic conditions | DIN IEC 721 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | < 95 % non-condensing |
Pollution degree | max. 2, according to IEC 60664 |
Mechanical specifications |
Connection type | Terminals |
Core cross-section | up to 2.5 mm2 |
Housing | 20 mm x 115 mm x 107 mm |
Degree of protection | IP20 |
Mass | approx. 100 g |
Mounting | DIN rail mounting |
International approvals |
UL approval | UL E106378, CUL E106378 |
| Approved for | Class I, Division 2, Groups A, B, C, D |
Classifications
System | Classcode |
ECLASS 13.0 | 27242611 |
ECLASS 12.0 | 27242611 |
ECLASS 11.0 | 27242611 |
ECLASS 10.0.1 | 27242611 |
ECLASS 9.0 | 27242611 |
ECLASS 8.0 | 27242611 |
ECLASS 5.1 | 27242611 |
ETIM 9.0 | EC002583 |
ETIM 8.0 | EC002583 |
ETIM 7.0 | EC002583 |
ETIM 6.0 | EC002583 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121004 |
Details:
KLD2-PC-1.1.IEC
Product Documentation:
KLD2-PC-1.1.IEC
Approvals:
KLD2-PC-1.1.IEC
Productos asociados:
KLD2-PC-1.1.IEC
Accessories |
|
|
|
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa |
|
|
|
|
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa |
|
|
|
|
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa |
|