Solenoid Driver HiC2883

HiC2883
  • 1-channel isolated barrier
  • 24 V DC supply (bus or loop powered)
  • Output 45 mA at 12 V DC
  • Line fault transparency (LFT)
  • Test pulse immunity
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2883

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage19 ... 30 V bus powered via Termination Board
19 ... 30 V loop powered via input , reverse polarity protected
Input current75 mA at 24 V, 270 Ω load
Power dissipation1.3 W at 24 V, 270 Ω load
Input
Connection sidecontrol side
ConnectionSL1: 7a(-), 9a(-); 8a(+), 10a(+)
Test pulse lengthmax. 2 ms from DO card
Signal levelloop powered
1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
bus powered
1-signal: 15 ... 30 V DC (current limited to 5 mA)
0-signal: 0 ... 5 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current< 200 mA , 10 ms loop powered
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Internal resistorapprox. 240 Ω
Currenttyp. 45 mA
Voltage≥ 12 V
Current limit50 mA
Open loop voltagetyp. 24.6 V
Loadnominal 0.05 ... 18 kΩ
Switching frequencymax. 10 Hz
Energized/De-energized delay20 ms / 5 ms
Line fault detection
Short-circuit< 25 Ω
Open-circuit> 50 kΩ
Test current< 500 µA
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Galvanic isolation
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017 , IEC/EN 61326-3-2:2018
For further information see system description.
Degree of protectionIEC 60529:2013
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 4 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateFIDI 21 ATEX 0069X
MarkingEx-Hexagon II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Voltage26 V
Current110 mA
Power715 mW
Supply
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
FM approvalFM 17 US 0111 X , FM 17 CA 0057 X
Control drawing116-0442
UL approvalE106378
Control drawing116-0447A (cULus)
IECEx approval
IECEx certificateIECEx EXA 17.0009X
IECEx markingEx nC ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiC2883

Function

This isolated barrier is used for intrinsic safety applications.

It supplies power to solenoids, LEDs and audible alarms located in a hazardous area.

The device is controlled with a loop powered signal or a bus powered logic signal.

The device is immune to the test pulses of various control systems.

The device simulates a minimum load at the input. The minimum load can be activated and de-activated.

The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver.

The line fault transparency function is only available, if the device is supplied via the termination board.

Product Documentation: HiC2883

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF151 KB
Functional Safety ManualENGPDF1959 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2883

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---

Approvals: HiC2883

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada FMFM 17 CA 0057XALLPDF328 KB
China SITIIAS CCC Ex Certificate2023322316004972 (Singapore)ALLPDF1265 KB
Europe Fiditas ATEX Category 3 (1) G Group I (M1) ATEX Category (1) DFIDI 21 ATEX 0069XALLPDF2500 KB
India PESO (India) CCOEA/P/HQ/KA/104/6095 (P579046)ALLPDF106 KB
Korea KOSHA18-AV4BO-0217XALLPDF518 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20181210 - E106378 RepRef 20181203ALLPDF478 KB
USA FMFM 17 US 0111XALLPDF330 KB
United Kingdom CML UKEX Category (1) D UKEX Category (M1) UK-Type Examination Certificate UKEX Category 3 (1) GCML 21UKEX21331XALLPDF160 KB
Worldwide EXA IECEx Certificate of ConformityIECEx EXA 17.0009XALLLINK---
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF136 KB
Control drawing FM / Control drawing FM   ALLPDF307 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3566CALLPDF404 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5696ALLPDF80 KB

Associated Products: HiC2883

Accessory of
System board for Yokogawa ProSafe-RS, For 8-channel DO card SDV531, For 8 modules, Recommended modules: HiC2883 (DO), HiC5861 (DO), HiC5863 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 8, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RSpa
Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.