Multi-Input/Output Junction Box, Polyester (GRP) F.MIO.P12.*12.P.*.***.***.**00

F.MIO.P12.*12.P.*.***.***.**00
  • For discrete inputs and outputs
  • Glass fiber reinforced polyester, impact resistant, IP66
  • Configurable cable entries for bus lines and field signal lines
  • International approvals
  • For PROFIBUS PA
  • Installation in Zone 1/Div. 1, intrinsically safe
  • Sensors in Zone 0/Div. 1

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  F.MIO.P12.*12.P.*.***.***.**00

General specifications
Design / MountingOutside installation
Installed componentsBinary multi-input/output R8D0-MIO-Ex12.PA* , For technical data on installed electronic component see data sheet.
Fieldbus connection
Fieldbus typePROFIBUS PA
Conformity
Degree of protectionEN 60529
Impact resistanceEN 60079-0
Ambient conditions
Ambient temperature-30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Impact resistance7J
Mechanical specifications
Enclosure coverdetachable cover with retaining screws
Degree of protectionIP66
Cable entrycable gland and stopping plug options see separate table
Material
Housingpolyester , impact resistant, glass fiber reinforced
Surfaceblack molded finish (RAL 9005)
Surface resistance< 109 Ω
Water absorption< 6 %
Sealsilicone , one-piece
Grounding platebrass
Material thicknessgrounding plate: 3 mm
Dimensions(W x H x D)
271 x 271 x 136 mm
Mountingthru-holes Ø6.5 mm
Groundinggrounding bolt M6 , Stainless steel
Data for application in connection with hazardous areas
EU-type examination certificatePTB 07 ATEX 1061 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 2(1)G Ex ib [ia Ga] IIC T4 Gb
Ex-Hexagon II 2(1)D Ex tb [ia Da] IIIC T135°C Db
CertificatePTB 17 ATEX 1011 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 3(1)G Ex ic [ia Ga] IIC T4 Gc
Ex-Hexagon II 3(1)G Ex ec [ia Ga] IIC T4 Gc
Ex-Hexagon II 3(1)D Ex tc [ia Da] IIIC T135°C Dc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014
International approvals
IECEx approvalIECEx PTB 07.0036 X , Zone 1 , suitable Junction Box on request
IECEx PTB 09.0016 X , Zone 2 , suitable Junction Box on request
INMETRO approvalTÜV 13.1143
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F.MIO.P12.*12.P.*.***.***.**00

Function

This fieldbus junction box holds a multi-input/output (MIO) for transferring signals from discrete inputs and valves to the control system. The MIO offers the same functionality as components FD0-VC-Ex* and FD0-BI-*. The fieldbus junction box can be installed in Zone 1 with sensors and actuators located in Zone 0.

Glass fiber reinforced polyester provides corrosion resistance and is lightweight. The surface resistance avoids electrostatic charge.

Bus and field signal line entries can be chosen individually from a range of cable glands and stopping plugs. A breather drain is included by default. Tag plate and grounding bar are available as options.

This fieldbus junction box is available pre-wired, with all accessories, for fast ordering, delivery, site installation, and commissioning.

Informative Literature: F.MIO.P12.*12.P.*.***.***.**00

Nyelvválasztás:
LiteratureNyelvFájltípusFájlméret
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F.MIO.P12.*12.P.*.***.***.**00

Nyelvválasztás:
Safety and Security DocumentationNyelvFájltípusFájlméret
Használati útmutatóHUNPDF152 KB
Manuals
ManualENGPDF767 KB

Approvals: F.MIO.P12.*12.P.*.***.***.**00

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
Brasil TUV Rheinland BrazilTÜV 13.1143ALLPDF1259 KB
Europe PTB ATEX Category 2 G ATEX Category 2 DPTB 07 ATEX 1061 XALLPDF500 KB
United Arab Emirates SGS Gulf Limited ECASEx23-10-87482/E23-09-089609ALLPDF850 KB
Worldwide PTB IECEx Certificate of Conformity CertificateIECEx PTB 07.0036XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3884BALLPDF132 KB

Kapcsolódó termékek: F.MIO.P12.*12.P.*.***.***.**00

Matching System Components

Multi-Input/Output Device for Cabinet Installation, For discrete inputs and outputs, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Zone 1/2 - intrinsically safe high-power trunk
Zone 1 - intrinsically safe trunkpa
For discrete inputs and outputs, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Multi-Input/Output Device for Cabinet Installation, For discrete inputs and outputs, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Zone 1/2 - intrinsically safe high-power trunk
Zone 1 - intrinsically safe trunkpa

Az Ethernet-APL lehetővé teszi a folyamatos adatátvitelt a hierarchia összes szintjén. Részletesen az úttörő technológiáról…

RSS információs szolgáltatás a PANOS frissítésekkel kapcsolatban

Bármikor tájékozódhat, ha az Ethernet-APL switch-ekoperációs rendszerének, a PANOS-nak új szoftverfrissítése jelenik meg: Az RSS-hírcsatornával azonnal kap egy e-mailes értesítést a postaládájába, miután egy frissítés megjelent.

A döntéshozataltól a tervezésig, a telepítésig, az üzembe helyezésig, valamint a működtetésig és karbantartásig: Fedezze fel, hogyan hozhatja ki a legtöbbet a terepi busz infrastruktúrából ...