Ex pxb and Ex pyb purge and pressurization system 6500-01-*-PNO-LNO

6500-01-*-PNO-LNO
  • Automatic purge and pressurization system for most applications
  • User-friendly, easy programming
  • LCD screen for operation status and LEDs for quick visual system identification
  • HART communication via RS-485 with PACTware and device app via Bluetooth
  • Maximum enclosure size 12.75 cubic meters
  • Compact design with panel mounts or direct mounts available
  • Universal power 20 to 30 VDC / 100 to 250 VAC. 50 to 60 HZ
  • Pressure, temperature, dilution control and monitoring
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  6500-01-*-PNO-LNO

Termék leírása
6500 series Ex pxb and Ex pyb purge and pressurization system
General specifications
Operating modeuser programmable
Series6500
Number of volume exchanges5 to 19
Hazardous environmentgas, dust, gas and dust
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Rated voltage100 ... 240 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC
Electrical specifications
ConnectionEPCU: Terminal blocks and grounding screw
UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters
Input type: intrinsically safe
Interface
Physical Bluetooth® 4.1
Transmitter frequency2.402 ... 2.485 MHz
Transmitter radiated power-19 ... 7.5 dBm
Sensitivity-92.5 dBm at 0.1 % BER
Detection range100 m in air
AntennaPCB
Communication
Bluetoothdeclaration ID: D037849
Input
Input IVoltage free contact or namur proximity sensor
Input typeIntrinsically Safe, Ex ib
Input II(1) 2-wire, PT100 RTD
Input typeIntrinsically Safe, Ex ib
Output
Output IAUX
Output typeVoltage free contact outputs, SPDT configuration
Inrush current2 A
Contact loading2 A @ 240VAC, resistive, 2 A @ 24VDC
Output IIEnclosure
Output typeVoltage free contact outputs, 2 N.O. configuration
Inrush current8 A
Contact loading8A @ 240 V AC, resistive up to 60 °C
8A @ 24 V DC up to 60 °C
5A @ 240 V AC, resistive, 60 to 70 °C
5A @ 24 V DC up to 60 to 70 °C
FuseExternal fusing is required at no more than 11 amps/1500 A breaking current
Output IIIDigital valve
When used with the 6500-MAN-DV-01, intrinsically safe
Internal resistance 280 Ω
Output IVProportional valve
When used with the 6500-MAN-PV-01, intrinsically safe
Current: 4 to 20 mA
Max. load: 300 Ω
CommunicationHART via RS485 (PACTware available)
Indicators/settings
Display elements2x20 LCD for configuration, monitoring, and status of the 65000 system with back light and contrast selection. Capacitive touch buttons
LED indicationSafe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault
Key: green - a button on the capacitive touch display has been activated. Momentary indication
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirementFor 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120psig) regulated
For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated
Note: max. pressure will depend on the vent model used. regulated
Safe pressureGas: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Gas+Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Valve flowsStandard vent series: EPV-6500-*-01, 03, 05
Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm).
Minimum and maximum reading depending on type of vent and supply pressure.
See data sheet for EPV-6500 series vent.
Continuous (Dilution) vent series: EPV-6500-*-07, 08
Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading.
Maximum reading depending on type of vent and supply pressure.
See data sheet for EPV-6500 series vent.
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity5 ... 85 %, non-condensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typeSee mounting in 6500 manual and cable gland requirements
Cable glandCable gland requirement: cable glands are not included. Customer can supply there own approved glands or use one of the 6500-CBLG-... cable gland kits.
I.S.cable glands: requires (5) M12 approved cable glands
Power cable glands: requires (2) M20 and (2) M12 approved cable glands
Degree of protectionIP66
MaterialUIC display: Makrolon FI cover and A380 Aluminum anodized casing
Housing: 316L stainless steel
Hardware: 316L stainless steel
Massapprox. 5 kg (11.0 lbs)
Dimensions6500-01-EXT1: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7")
6500-01-PM01: 150 x 150 x 185 mm (5.9" x 5.9" x 7.3")
6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7"), UIC: 150 x 150 x 45 mm (5.9" x 5.9" x 1.8")
Data for application in connection with hazardous areas
EU-type examination certificateATEX UL / DEMKO 15 ATEX 1622X
Directive conformity
Directive 94/9/ECEN 60079-0:2012 , EN 60079-2:2014 , EN 60079-11:2011
International approvals
IECEx approvalIECEx UL / DEMKO 15.0147X

General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: 6500-01-*-PNO-LNO

ManualsNyelvFájltípusFájlméret
6500 Series Installation & Operation Manual (US English)ENGPDF4068 KB
Functional Safety ManualENGPDF1625 KB
Short instructions, safety information
Purge & Pressurization Smart App - Users Guide / Purge & Pressurization Smart App - Users GuideALLPDF1771 KB

Approvals+Certificates: 6500-01-*-PNO-LNO

Statements of complianceTanúsítvány sz.FájltípusFájlméret
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-B080PDF161 KB
Certificates
ATEX CertificateDEMKO 16 ATEX 1640XPDF1087 KB
Bluetooth SIG Radio ApprovalD037849LINK---
IECEx Certificate of ConformityIECEx UL 16.0003XLINK---
exida Functional SafetyP+F 1601040 P0006 C016 V1R0PDF405 KB

Software: 6500-01-*-PNO-LNO

Device type managersMegjelenési információFájltípusFájlméret
DTM for 6500 Series / DTM_aZIP21548 KB

Function: 6500-01-*-PNO-LNO

The 6500 series purge and pressurization system consists of a control unit, an EPV-6500 enclosure protection vent, and a valve for pressurization, purging, and, with some models, dilution for analyzer applications.

The compact 6500 control unit features an LCD user interface with sealed capacitive touch buttons. LEDs provide quick indication of the system status. The control unit has an input for a 2-wire RTD for temperature control/monitoring. Models are available that allow the user interface to be panel mounted to an enclosure wall or mounted onto the exterior of the enclosure. A HART output allows the control unit to be connected to a PC using PACTware or the customer’s AMS for remote monitoring. An app for Android, BlackBerry, and Apple devices allows connectivity via Bluetooth®.

Ismerje meg, hogyan biztosíthatja a legokosabb módon a robbanásveszélyes helyek védelmét, és konfigurálhatja saját öblítő- és nyomásfokozó rendszerét!

Öblítésvezérlő alkalmazás

A Pepperl+Fuchs új „6500” öblítésvezérlő alkalmazása valós idejű megfigyelést és konfigurációt biztosít a 6500 sorozatú öblítő- és nyomásfokozó rendszerhez. Töltse le az alkalmazást iOS vagy Androidos készülékére…