Serviceline Industrial Sensors
Serviceline Explosion Protection

Process control and indication equipment DA6-IU-2K-V

DA6-IU-2K-V
  • 2 adjustable trip values
  • 2 relay outputs
  • Operation via keypad
  • Characteristic programmable via 12 interpolation points
  • Resetting the outputs, automatic, manual or with external signal
  • Connection via plug-in screw terminals
  • Auxiliary power output for sensors
  • Degree of protection IP65 in accordance with DIN EN 60529 (front only)
  • System hum suppression

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  DA6-IU-2K-V

Product Description
Process control and indication equipment
General specifications
Pre-selection2-fold
Data storage> 10 years, EEPROM
Programmingkeypad-driven menu
Indicators/operating means
Type14-segment LED display, red
Number of digits6
Display valuedigit height 14 mm
Key interlockwith "high"-level at terminal "KEY"
Display interval-199999 ... 999999
with suppression of leading zeros
Decimal pointfreely adjustable
Resolution15 Bit
Scale factorvia characteristic curve with up to 12 value pairs
Resetmanually or external
Electrical specifications
FusingT 0.1 A
Operating voltage90 ... 260 V AC
Power consumption9 VA
Input
Impedance> 1 MΩ for voltage measurement
< 50 Ω for current measurement
Analog voltage input0 ... 10 V / 2 ... 10 V DC,
-10 ... 10 V DC
Analog current input0 ... 20 mA / 4 ... 20 mA
Output
Relaychangeover contact
Switching voltagemax. 250 V AC / 125 V DC
min. 5 V AC / 5 V DC
Switching currentmax. 5 A AC / 5 A DC
min. 10 mA DC
Switching powermax. 1250 VA / 150 W
Sensor supply24 V DC ± 15 % , 30 mA
15 V DC ± 1 %, 25 mA
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61000-6-2:2006 (With shielded signal and control lines)
DIN EN 55011:2009, Class B
Standard conformity
Galvanic isolationEN 61010-1:2010
Degree of protectionEN 60529:1991 + A1:2000
Shock and impact resistanceEN 60068-2-27:2009
EN 60068-2-29:1995
Vibration resistanceEN 60068-2-6:2008
Ambient conditions
Ambient temperature-10 ... 50 °C (14 ... 122 °F)
Storage temperature-20 ... 70 °C (-4 ... 158 °F)
Relative humidity≤ 80 % (noncondensing)
Mechanical specifications
Degree of protectionIP65 (front)
Connection8-pin and 9-pin connectors with screw terminals
Mass180 g
Dimensions96 mm x 48 mm x 102 mm
Mountingmounting frame with latch fastener

Classifications

SystemClasscode
ECLASS 13.027210301
ECLASS 12.027210301
ECLASS 11.027210301
ECLASS 10.0.127210301
ECLASS 9.027210301
ECLASS 8.027210301
ECLASS 5.127210301
ETIM 9.0EC002300
ETIM 8.0EC002300
ETIM 7.0EC002300
ETIM 6.0EC002300
ETIM 5.0EC000677
UNSPSC 12.143211906

Details: DA6-IU-2K-V

Product Documentation: DA6-IU-2K-V

Language Selection:
ManualsLanguageFile TypeFile Size
ManualENGPDF3411 KB

Approvals: DA6-IU-2K-V

Language Selection:
Declaration of ConformityCertificate No.LanguageFile TypeFile Size
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2895BALLPDF110 KB