SMART Transmitter Power Supply HiD2022

HiD2022
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Output 4 mA ... 20 mA, current source
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  HiD2022

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage18 ... 30 V DC bus powered via Termination Board
Ripplewithin the supply tolerance
Power dissipation≤ 1.4 W
Power consumption≤ 2.6 W
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Input signal4 ... 20 mA , current limit 27 mA
Input resistancemax. 265 Ω SL2: 5b, 7a; 1b, 3b ; max. 330 Ω SL2: 5a, 7a; 1a, 3b
Available voltage≥ 16 V at 20 mA , SL2: 5a(+), 5b(-); 1a(+), 1b(-)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Load0 ... 650 Ω
Output signal4 ... 20 mA (overload > 25 mA)
Ripplemax. 50 µA rms
Transfer characteristics
Deviationat 20 °C (68 °F), 4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature≤ 0.25 µA/K
Frequency rangefield side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Settling time200 µs
Rise time/fall time100 µs
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Height114 mm
Width18 mm
Depth130 mm
Mountingon termination board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCML 17 ATEX 2143X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
EquipmentSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Voltage26.2 V
Voltage27.25 V
Current93 mA
Power634 mW
EquipmentSL2: 5b(+), 7a(-); 1b(+), 3b(-)
Voltage30 V
Current115 mA
Powermax 1 W
Voltage2 V
Current8.5 mA
Power4.3 mW
EquipmentSL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Voltage26.2 V
Voltage27.25 V
Current115 mA
Power784 mW
CertificateCML 17 ATEX 3144X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
IECEx approval
IECEx certificateIECEx CML 17.0072X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2022

Product Documentation: HiD2022

Language Selection:
Safety and Security DocumentationLinguaFile tipoDimensioni
Manuale di istruzioniITAPDF162 KB
Functional Safety ManualENGPDF1974 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiD2022

Language Selection:
CADLinguaFile tipoDimensioni
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ38 KB

Approvals: HiD2022

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
CML [Ex ia] Ex ec IECEx Certificate of ConformityIECEx CML 17.0072XALLLINK---
China SITIIAS CCC Ex Certificate2020322316003277 (Singapore)ALLPDF1587 KB
Europe CML ATEX Category 3 GCML 17 ATEX 3144XALLPDF124 KB
Europe CML I (M1) II (1) D ATEX II (1) GCML 17 ATEX 2143XALLPDF140 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3714AALLPDF48 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.