ファクトリーオートメーション(FA)
プロセスオートメーション(PA)

Solenoid Driver KFD2-VM-Ex1.35.L

KFD2-VM-Ex1.35.L
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 15.3 V DC at 17 mA
  • 3 logic inputs with AND/OR logic
  • Service port for isolator function test

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  KFD2-VM-Ex1.35.L

General specifications
Signal typeDigital Output
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 52 mA
Power dissipationtyp. 1.2 W
Power consumption< 1.5 W
Input
Connection sidecontrol side
Connectionterminals 7+, 8+, 9+
Signal level1-signal: 15 ... 30 V DC ; input current: approx. 2.3 mA at 24 V DC
0-signal: 0 ... 5 V DC or open input
Response delay5 ... 30 ms (typical 10 ms)
Output
Connection sidefield side
Internal resistormax. 410 Ω
Currenttyp. 18 mA
Voltagetyp. 16 V
Limitcurrent IE: ≥ 17 mA; typ. 18 mA
voltage UE: ≥ 15.3 V; typ. 16 V
Open loop voltagemin. 22.3 V
Connectionterminals 4+, 6-
Output current17 mA
Output signalThese values are valid for the rated operating voltages from 20 ... 30 V DC.
Transfer characteristics
Switching frequency15 Hz
Galvanic isolation
Input/power supplynot available
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Height107 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2132
MarkingEx-Hexagon II (1)GD [Ex ia] IIC [circuit(s) in zone 0/1/2]
OutputEx ia
Voltage25.2 V DC
Current67.2 mA
Power423.5 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC/125 V DC without jumper 10-11, 60 V with jumper 10-11 (Attention! Um is no rated voltage.)
Input
Maximum safe voltage60 V (Attention! Um is no rated voltage.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KFD2-VM-Ex1.35.L

Informative Literature: KFD2-VM-Ex1.35.L

Language Selection:
Literature言語ファイルタイプファイルサイズ
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-VM-Ex1.35.L

Language Selection:
Product information言語ファイルタイプファイルサイズ
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
Instruction manualENGPDF49 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-VM-Ex1.35.L

Language Selection:
CAD言語ファイルタイプファイルサイズ
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ56 KB

Approvals: KFD2-VM-Ex1.35.L

Language Selection:
Certificates認証番号言語ファイルタイプファイルサイズ
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2132ALLPDF554 KB
Pepperl+Fuchs Functional Safety AssessmentFS-0065PF-20A ALLPDF69 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1949AALLPDF52 KB

関連製品: KFD2-VM-Ex1.35.L

Matching System Components
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.