ファクトリーオートメーション(FA)
プロセスオートメーション(PA)

Not available for purchase

This product has been replaced.Go to replacement product LB8122A.1.EL
Not available for purchase
Not available for purchase

Gateway for PROFINET LB8122A.1.EL

LB8122A.1.EL
  • Interface between the I/O modules and the PCS/PLC
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Non-volatile memory for configuration and parameter settings
  • Communication via PROFINET
  • HART communication via HART I/P

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  LB8122A.1.EL

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Nominal voltage12 V DC ,
Power dissipation4.53 W
Power consumption4.53 W
Fieldbus connection
Fieldbus typePROFINET
Ethernet Interface
Connection typeRJ-45 , via front connector
Transfer rate10BASE-T, 100BASE-TX 100 MBit/s
Station connectiondirectly to PCS or PLC or via hubs or switches
Cable typeSFTP in accordance with ISO/IEC 11801 for Cat 5e or better
Bus lengthmax. 100 m per link
AddressingDHCP, via controller (DCP) or fixed IP address
Ethernet addressIP V4 address (preset: DHCP on, changeable via display)
Supported I/O modulesLB1x01*…LB1x03*, LB1x08*, LB1x09*, LB2x01*…LB2x17*, LB3x01*…LB3x06*, LB4x01*, LB4x02*, LB4x04*…LB4x06*, LB5x01*, LB5x02*, LB5x04*…LB5x06*, LB6x01*, LB6x05*, LB6x06*, LB6x08*, LB6x10*…LB6x17*, LB7x04*
HART communicationvia PROFINET and HART I/P
PROFINET conformance classCC B
Internal bus
Connectionbackplane bus
Galvanic isolation
Ethernet/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
RS 485 interface/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
Insulation voltage1500 V AC acc. to IEEE 802.3u
Electrical isolation
Power supply, internal bus/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Degree of protectionIEC 60529
Fieldbus standardIEEE 802.3
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , mounted on backplane
Connectionvia backplane
Massapprox. 150 g
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
CertificateDEMKO 16 ATEX 1780 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013
EN 60079-15:2010

International approvals
ATEX approvalDEMKO 16 ATEX 1780 X
IECEx approvalIECEx UL 16.0141 X
Approved forEx nA IIC T4 Gc
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: LB8122A.1.EL

Informative Literature: LB8122A.1.EL

Language Selection:
Literature言語ファイルタイプファイルサイズ
Application Report - Communication Redundancy for Uninterrupted OperationENGPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesENGPDF208 KB
Application Report - Space Saving Extension for Existing PlantsENGPDF300 KB

Product Documentation: LB8122A.1.EL

Language Selection:
Product information言語ファイルタイプファイルサイズ
Release NoteENGPDF383 KB
Brief Instructions
Configuration instructions STEP 7ENGPDF3870 KB
Configuration instructions TIA PortalENGPDF4041 KB
Safety and Security Documentation
Instruction manualENGPDF152 KB
Manuals
CFC for STEP 7ENGPDF1447 KB
ManualENGPDF5915 KB
Manual LB HardwareENGPDF6842 KB
Software Information
Software Product Note Remote I/O DTM / Softwareproduktschein Remote I/O DTMALLPDF256 KB

Design / Simulation: LB8122A.1.EL

Language Selection:
CAD言語ファイルタイプファイルサイズ
CAD 3-D / CAD 3-DALLSTP1977 KB

Approvals: LB8122A.1.EL

Language Selection:
Certificates認証番号言語ファイルタイプファイルサイズ
China SITIIAS CCC Ex Certificate2021322310003602 (Mannheim)ALLPDF1085 KB

Software: LB8122A.1.EL

Language Selection:
Device Description Files/DriversRelease Infoファイルタイプファイルサイズ
DTM / DTMLBFB HART IPZIP9478 KB
CFC Device Driver Blocks for SIMATIC PCS 7 / CFC Device Driver Blocks for SIMATIC PCS 7ZIP15869 KB
PROFINET Gateway

The new LB/FB PROFINET gateways from Pepperl+Fuchs open the door for IIoT 4.0 applications in process industries.