ファクトリーオートメーション(FA)
プロセスオートメーション(PA)

Fieldbus Surge Protector, Trunk Installation on Power Hub TPH-LBF-IA1.36.DE*

TPH-LBF-IA1.36.DE*
  • Pluggable, mounts between Power Hub and trunk cable
  • Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose
  • Optional diagnostics for wear
  • Grounding of shield direct
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Indication via LED and Advanced Diagnostics

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  TPH-LBF-IA1.36.DE*

General specifications
Design / MountingCabinet installation
Fieldbus connection
Self current consumptionmax. 6 mA (for version TPH-LBF-IA1.36.DE.1) , max. 0 mA (for version TPH-LBF-IA1.36.DE.0)
Indicators/operating means
LED ERRgreen flashing: status OK , red flashing: maintenance required , (for version TPH-LBF-IA1.36.DE.1)
Electrical specifications
Rated voltage36 V
Rated current600 mA
Voltage protection level
Line/Linemax. 50 V category B2 10/700 µsec , 25 A
max. 52 V category C1 8/20 µsec , 300 A
max. 55 V category C2 8/20 µsec , 5 kA
max. 46 V category C3 1 kV/µsec , 10 A
Line/Earthmax. 1060 V category B2 10/700 µsec , 50 A per line
max. 800 V category C1 8/20 µsec , 300 A per line
max. 1450 V category C2 8/20 µsec , 5 kA per line
max. 1300 V category C3 1 kV/µsec , 50 A per line
max. 1080 V category D1 10/350 µsec , 500 A per line
Reaction time
Line/Linemax. 1 ns
Line/Earthmax. 100 ns
Overstressed fault modeacc. IEC 61643-21 line inoperable mode 3
Series resistance in line2 Ω +/- 5 %
Impulse durability
Per line5 kA category C2 8/20 µsec
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNAMUR NE 21
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Surge protectionIEC 61643-21
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typescrew terminals
Core cross sectionflexible wire 2.5 mm2 solid wire max. 4 mm2
Housing materialPolyamide PA 6.6
Degree of protectionIP20
Mass45 g
GroundingM4 screw and external grounding rail
Data for application in connection with hazardous areas
EU-type examination certificateSIRA 12 ATEX 2128X
MarkingEx-Hexagon II 1G Ex ia IIC T4
Voltage24 V
Current500 mA
Internal capacitance2 nF
Internal inductance0.1 µH
CertificateSIRA 12 ATEX 4176X
MarkingEx-Hexagon II 3G Ex nAc IIC T4 , Ex-Hexagon II 3G Ex ic IIC T4 Class I and II, Division 1, Group C - G
Voltage Ui33 V
Current Ii600 mA
Internal capacitance Ci2 nF
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007
Supplementary informationFISCO field device
International approvals
CSA approvalCoC 2595441
Control drawing116-0365
Approved forClass I, Division 1, Groups A, B, C, D T4
Class I, Zone 1, Ex ia IIC T4
Class I, Zone 2, Ex ic IIC T4
Class I, Zone 0, AEx ia IIC T4
Class I, Zone 2, AEx ic IIC T4
Class I, Division 2, Groups A, B, C, D T4
Class I, Zone 2, Ex nL IIC T4
Class I, Zone 2, Ex na IIC T4
Class I, Zone 2, AEx nAc IIC T4
IECEx approvalIECEx SIR 12.0051X
Approved forEx ia IIC T4
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.019170104
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC001604
UNSPSC 12.139121610

Details: TPH-LBF-IA1.36.DE*

Informative Literature: TPH-LBF-IA1.36.DE*

Language Selection:
Literature言語ファイルタイプファイルサイズ
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: TPH-LBF-IA1.36.DE*

Language Selection:
Safety and Security Documentation言語ファイルタイプファイルサイズ
Instruction manualENGPDF227 KB
Manuals
Manual Fieldbus Surge Protector, TPH-LBF-IA1.36* , TCP-LBF-IA1.36* , SCP-LBF-IA1.36*ENGPDF6301 KB

Design / Simulation: TPH-LBF-IA1.36.DE*

Language Selection:
CAD言語ファイルタイプファイルサイズ
CAD 2-D / CAD 2-DALLZIP236 KB

Approvals: TPH-LBF-IA1.36.DE*

Language Selection:
Certificates認証番号言語ファイルタイプファイルサイズ
Brasil TUV Rheinland BrazilTÜV 14.1589 XALLPDF1153 KB
Canada, USA CSA Ex i and Ex nCSA 13.2595441XALLPDF114 KB
China SITIIAS CCC Ex Certificate2020322304003528 (Singapore)ALLPDF1024 KB
Europe CSA ATEX Category 1 GSira 12 ATEX 2128XALLPDF215 KB
Europe CSA ATEX Category 3 G II 3 GSira 12 ATEX 4176XALLPDF228 KB
India PESO (India) CCOEA/P/HQ/KA/104/5866 (P506129)ALLPDF100 KB
Sira IECEx Certificate of ConformityIECEx SIR 12.0051XALLLINK---
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF92 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0814CENGENGPDF1142 KB

関連製品: TPH-LBF-IA1.36.DE*

Accessory of
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnostics, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …