ファクトリーオートメーション(FA)
プロセスオートメーション(PA)

Not available for purchase

This product has been replaced.Go to replacement product KFD2-SH-Ex1.T.OP
Not available for purchase
Not available for purchase

Switch Amplifier KFD2-SH-Ex1.T.OP

KFD2-SH-Ex1.T.OP
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for approved dry contacts or SN/S1N sensors
  • Active voltage output
  • Relay contact output
  • Fault indication output
  • Line fault detection (LFD)
  • Up to SIL 3 acc. to IEC/EN 61508
  • Up to PL d acc. to EN/ISO 13849

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  KFD2-SH-Ex1.T.OP

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL d
Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 100 mA
Power dissipation1.5 W
Power consumptionmax. 1.7 W
Input
Connection sidefield side
Connectionterminals 4+, 6-
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistancemax. 50 Ω , cable capacitances and inductances must be observed in hazardous areas
Switching point
Relay de-energizedI < 2.1 mA and I > 5.9 mA , output switched off
Relay energized2.8 mA < I < 5.3 mA , output switched on
Response delay≤ 1 ms
Output
Connection sidecontrol side
Connectionoutput I: terminals 7+, 8- ; output II: terminals 9, 10 ; output III: terminals 11, 12
Output Iactive voltage output, short-circuit proof
0-signal: 0 V
1-signal: 20 ... 31 V DC at max. 15 mA
fault: 0 V
Output IIrelay
Contact loading48 V AC/DC
250 mA
Mechanical life≤ 20 x 106 switching cycles
Output IIIrelay , fault signal
Contact loading48 V AC/DC
250 mA
Mechanical life≤ 20 x 106 switching cycles
Transfer characteristics
Switching frequency
Output I≤ 50 Hz
Output II≤ 5 Hz
Output III≤ 5 Hz
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Machinery Directive
Directive 2006/42/ECEN/ISO 13849-1:2015
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
SafetyIEC/EN 61508:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Height107 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2041
MarkingEx-Hexagon II (1)GD [Ex ia] IIC [circuit(s) in zone 0/1/2]
InputEEx ia IIC
Voltage9.56 V
Current16.8 mA
Power41 mW (linear characteristic)
Supply
Maximum safe voltage40 V AC/DC (Attention! The rated voltage can be lower.)
Output
Contact loading48 V AC/DC
250 mA
Maximum safe voltage60 V AC/DC (Attention! The rated voltage can be lower.)
CertificateTÜV 99 ATEX 1493 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0158
IECEx approval
IECEx certificateIECEx TUN 19.0013X
IECEx markingEx ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SH-Ex1.T.OP

Product Documentation: KFD2-SH-Ex1.T.OP

Language Selection:
Safety and Security Documentation言語ファイルタイプファイルサイズ
Instruction manualENGPDF149 KB
Original Instructions/Functional Safety ManualENGPDF660 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-SH-Ex1.T.OP

Language Selection:
CAD言語ファイルタイプファイルサイズ
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ60 KB

Approvals: KFD2-SH-Ex1.T.OP

Language Selection:
Certificates認証番号言語ファイルタイプファイルサイズ
DNV MarineTAA00001WXALLPDF114 KB
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2041ALLPDF422 KB
IECEx Certificate of ConformityIECEx PTB 21.0010ALLLINK---
Korea KOSHA11-AV4BO-0063ALLPDF569 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) G UKEX Category (1) DCML 23UKEX2154ALLPDF164 KB
Worldwide TÜV SÜD Functional Safety AssessmentPM85769TALLPDF797 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0594BALLPDF81 KB

関連製品: KFD2-SH-Ex1.T.OP

Matching System Components
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.