Serviceline Industrial Sensors
Serviceline Explosion Protection

WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2

WHA-UT-F7B1-0-PP-Z1-Ex2
  • 2-channel
  • Installation in Zone 1
  • WirelessHART converter
  • Battery operated
  • Thermocouple or RTD input
  • Output WirelessHART wireless interface
  • Internal antenna

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  WHA-UT-F7B1-0-PP-Z1-Ex2

Supply
Rated voltage3.6 V DC , battery operated
Power dissipation/power consumption< 0.09 W
Input
Connectionterminals 1, 2, 3, 4
RTDtype Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391)
Connection2-wire: 2 sensors, 3- or 4-wire: 1 sensor
Lead resistancemax. 10 Ω
Measuring circuit monitoringsensor breakage
Thermocouplestype E, J, K, T (IEC 584-1)
Cold junction compensationinternal , external
Measuring circuit monitoringsensor breakage
Measurement rangetype K: -270 ... 1370 °C
type T: -270 ... 400 °C
type E: -270 ... 1000 °C
type J: -210 ... 1200 °C
Resistor
Measurement range0 ... 500 Ω , 0 ... 4000 Ω
VoltagemV Input
Measurement range-100 ... 100 mV , 0 ... 300 mV
Input resistance≥ 1 MΩ
Output
Output variablesPV: input 1 (°C, Ω, mV)
SV: input 2 (°C, Ω, mV)
TV: CJC temperature (°C)
estimated battery life (days)
battery voltage (volts)
residual battery capacity (%)
Transfer characteristics
Accuracy- internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3)
- external cold junction compensation error ± 1 °C (typ.)
- resolution error < 0.1 °C
- accuracy TC ± 20 µV
- accuracy RTD: ± 100 mΩ
Indicators/settings
Parameter assignment- sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes
- transmit power: configurable 0 dBm or 10 dBm (EIRP)
- sensor type
- mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV)
- publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Radio and telecommunication terminal equipmentThe usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
Directive 99/5/ECETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001
FCC CFR47 Part 15 B and CANSI C63.4-2003
Conformity
Degree of protectionIEC 60529
AccuracyIEC 61298-3
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-20 ... 70 °C (-4 ... 158 °F)
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
test setup and execution acc. to EN 60068-2-60
Mechanical specifications
Degree of protectionIP65
Massapprox. 1000 g
Dimensions77 x 129 x 177 mm (3 x 5.08 x 6.97 inch)
Mountingpanel or pole mounting
Data for application in connection with hazardous areas
EC-Type Examination CertificateIMQ 09 ATEX 008X
Group, category, type of protectionEx-Hexagon II 2(1)G Ex ia [ia] IIC T4
Directive conformity
Directive 94/9/ECEN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007
International approvals
FM approvalCoC 3042534
IECEx approvalIECEx INE 09.0025X
Approved forEx ia IIC T4
Accessories
Designationbattery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately)
Mounting set W-ACC-F7MK
External cold junction compensation W-ACC-CJC

Documents: WHA-UT-F7B1-0-PP-Z1-Ex2

ManualsLanguageFile TypeFile Size
Manual WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2ENGPDF1413 KB
Instruction leaflets
Operating instructions WHA-UT-F7B1-0-PP-Z1-Ex2 / Betriebsanleitung WHA-UT-F7B1-0-PP-Z1-Ex2ALLPDF90 KB
Instruction manuals
Instruction manualENGPDF65 KB
BetriebsanleitungGERPDF66 KB
Short instructions, safety information
Quick Start Guide WirelessHART NetworkENGPDF2045 KB
Kurzanleitung WirelessHART NetzwerkGERPDF2049 KB
Product information
Software Release Notes WHA-UTENGPDF42 KB

CAD+CAE: WHA-UT-F7B1-0-PP-Z1-Ex2

CADFile TypeFile Size
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF)ZIP568 KB

Approvals+Certificates: WHA-UT-F7B1-0-PP-Z1-Ex2

CertificatesCertificate No.File TypeFile Size
Europe IMQ ATEX Category 2 (1)IMQ 09 ATEX 008XPDF425 KB
INERIS IECEx Certificate of ConformityIECEx INE 09.0025XLINK---
India Radio ApprovalETA 2192/2012/WRLOPDF513 KB
Japan CETECOM ICT Radio / Connection202-LSA064 / D 12-0051 202PDF181 KB
Korea Radio ApprovalKCC-RRM-PFG-WHA-UTPDF728 KB
USA FMCoC 3042534PDF171 KB

Software: WHA-UT-F7B1-0-PP-Z1-Ex2

DriversRelease InfoFile TypeFile Size
DD Collection for WirelessHART / DD Collection für WirelessHARTZIP3095 KB
Device type managers
DTM Collection WirelessHART V1.0.2.4 / DTM Collection WirelessHART V1.0.2.4ZIP22259 KB

Associated Products: WHA-UT-F7B1-0-PP-Z1-Ex2

Matching system components
MODBUS WirelessHART Gateway, Graphical network analysis, Simple and automatic configuration options, Ethernet and RS 485 interface, HART and MODBUS protocol via both interfaces, Input WirelessHART wireless interface, 24 V DC supply, Redundant power supply connectionspa
EtherNet/IP WirelessHART Gateway, Graphical network analysis, Simple and automatic configuration options, Ethernet and RS 485 interface, HART protocol via both interfaces, EtherNet/IP protocol via Ethernet interface, Input WirelessHART wireless interface, 24 V DC supply, Redundant power supply connectionspa
WirelessHART Adapter BULLET

The BULLET is the only WirelessHART adapter on the market in an Ex d housing. Simply connect the BULLET to your field device and enable efficient, wireless signal transmission.