Basic Segment Coupler KFD2-BR-1.PA.1500

KFD2-BR-1.PA.1500
  • Output: 24 ... 26 V/400 mA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • High-power trunk for high device count and long cable lengths
  • Installation in Zone 2/Class I, Div. 2
  • Up to 1.5 MBit auto-adapting
  • PROFIBUS DP terminator selectable
  • Power Rail support

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  KFD2-BR-1.PA.1500

General specifications
Design / MountingCabinet installation
Supply
ConnectionPower Rail or terminals 11 (L+), 12 (L-)
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current640 mA ... 365 mA
Power dissipationmax 2.5 W
Fieldbus connection
PROFIBUS PA
Connection3+, 6+, 2-, 5-, 1 shield, 4 shield
Rated voltage24 ... 26 V
Rated currentmax. 400 mA
Terminating impedance100 Ω , integrated
PROFIBUS DPPROFIBUS with RS-485 transmission technology
Connectionterminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE
Baud rate1.5 MBit/s max.
Indicators/operating means
SwitchPROFIBUS DP terminator
LED PWRgreen: Power on
LED DP/ERRred 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected
LED PAred 2 Hz flashing: No PA communication or overload Off: PA communication OK
Galvanic isolation
PROFIBUS DP/PROFIBUS PAfunctional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC
PROFIBUS DP/Supplybasic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
PROFIBUS PA/Supplybasic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNAMUR NE 21
Degree of protectionIEC/EN 60529
Fieldbus standardEN 50170/2
Climatic conditionsDIN IEC 721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Core cross-sectionup to 2.5 mm2
Housing materialPolycarbonate
Degree of protectionIP20
Mass180 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
CertificateTÜV 16 ATEX 7831 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-7:2015
International approvals
CSA approvalCSA 16.70064204
Approved forClass I, Division 2, Groups A, B, C, D
Class I, Zone 2, Ex nA IIC T4 Gc
IECEx approvalIECEx TUR 16.0006X
Approved forEx ec IIC T4 Gc
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 8.0EC001604
ETIM 7.0EC001604
ETIM 6.0EC001604
ETIM 5.0EC001604
UNSPSC 12.139121008

Documents: KFD2-BR-1.PA.1500

ManualsIdiomaTipo de archivoTamaño
ManualENGPDF1199 KB
Instruction manuals
Instruction manualENGPDF52 KB
Manuel d'instructionsFRAPDF54 KB
BetriebsanleitungGERPDF53 KB
Manuale di istruzioniITAPDF52 KB
Manual de instruccionesSPAPDF53 KB

Approvals+Certificates: KFD2-BR-1.PA.1500

Statements of complianceNúmero de CertificadoTipo de archivoTamaño
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2642APDF89 KB
Certificates
Canada, USA CSA Certificate of Compliance16.70064204PDF172 KB
EAC Lenpromexpertiza (LPE) EAC TP TC 012/2011EAEC RU C-DE.AA71.B.00037/19PDF2835 KB
Europe TUV Rheinland ATEX Category 3 GTÜV 16 ATEX 7831 XPDF172 KB
TUV Rheinland IECEx Certificate of Conformity Zone 2IECEx TUR 16.0006XLINK---

Software: KFD2-BR-1.PA.1500

Software ToolsLiberar InfoTipo de archivoTamaño
GSD converter for transparent gateways / GSD-Konverter für transparente GatewaysV1.3ZIP793 KB

Productos asociados: KFD2-BR-1.PA.1500

Accessories

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

Ethernet-APL permite una comunicación continua en todos los niveles jerárquicos. Obtenga más información sobre esta tecnología pionera...

Desde las decisiones a la planificación, instalación y puesta en marcha, hasta el funcionamiento y mantenimiento: descubra cómo sacar el máximo partido de su infraestructura de bus de campo…

La guía de la selección rápida de productos para la tecnología de interfaces, FieldConnex® y tecnologías de conexión de E/S remotas le ayudará a seleccionar la tecnología y los sistemas adecuados a la hora de diseñar plantas.