Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBN5-F7-E0

NBN5-F7-E0
  • 5 mm flush
  • 3-wire DC

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Ladda ned datablad som PDF::


Utdrag ur datablad: Tekniska data för  NBN5-F7-E0

General specifications
Switching functionNormally open (NO)
Output typeNPN
Rated operating distance5 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 4.05 mm
Reduction factor rAl 0.3
Reduction factor rCu 0.2
Reduction factor r304 0.7
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 500 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 3 V
Operating current0 ... 100 mA
Off-state current0 ... 0.5 mA typ. 0.1 µA at 25 °C
No-load supply current≤ 20 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd2980 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.14 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP67

Documents: NBN5-F7-E0

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF117 KB
EinbaubedingungenGERPDF118 KB
Documents
EPLAN macro EMA / EPLAN Makro EMAALLEMA91 KB

Approvals+Certificates: NBN5-F7-E0

Statements of complianceCert No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3479PDF185 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.