Fabrika Otomasyonu
Proses Otomasyonu

Inductive sensor NJ1,5-8GM-N-V1

NJ1,5-8GM-N-V1
  • 1.5 mm flush
  • Usable up to SIL 2 acc. to IEC 61508


NAMUR sensörler, onaylı anahtar yükselticilerle birlikte kullanılmalıdır. Uygun cihazları aşağıda bulabilirsiniz:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Tam veri sayfasını PDF olarak indirin:


Veri sayfası alıntısı: Teknik veriler  NJ1,5-8GM-N-V1

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance1.5 mm
Installationflush
Assured operating distance0 ... 1.215 mm
Actual operating distance1.35 ... 1.65 mm typ.
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 5000 Hz
Hysteresis1 ... 10 typ. 5 %
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
EAC conformityTR CU 012/2011
FM approval
Control drawing116-0165
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP67
General information
Use in the hazardous areasee instruction manuals

Documents: NJ1,5-8GM-N-V1

Instruction manualsDilDosya TipiDosya Boyutu
ИнструкцииBULPDF166 KB
Návod k poużitíCZEPDF159 KB
Instruktions manualDANPDF158 KB
Instruction manualENGPDF160 KB
KasutusjuhendESTPDF153 KB
KäyttöohjeFINPDF153 KB
Manuel d'instructionsFRAPDF160 KB
BetriebsanleitungGERPDF159 KB
Οδηγίες χρήσηςGREPDF168 KB
HandleidingHOLPDF158 KB
Instruction manual / BetriebsanleitungHRVPDF157 KB
Használati útmutatóHUNPDF162 KB
Manuale di istruzioniITAPDF159 KB
Lietošanas pamācībaLAVPDF157 KB
Instrukciju vadovasLITPDF159 KB
Instrukcja obsługiPOLPDF160 KB
Manual de instruçõesPORPDF160 KB
Manual de utilizareRONPDF161 KB
Návod na poużitieSLKPDF160 KB
Navodila za uporaboSLVPDF157 KB
Manual de instruccionesSPAPDF221 KB
ManualSWEPDF157 KB
Technical information
Installation conditionsENGPDF1054 KB
EinbaubedingungenGERPDF1060 KB

Approvals+Certificates: NJ1,5-8GM-N-V1

Statements of complianceSertifika No.Dosya TipiDosya Boyutu
EU-Declaration of conformity / EU-Konformitätserklärung DOC-1661APDF387 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 00 ATEX 2048 XPDF29071 KB
Pepperl+Fuchs Declaration of Conformity Functional SafetyPF13CERT1624BPDF1451 KB
Russia NANIO "CCVE"TC RU C-DE.AA87.B.00394PDF3971 KB
Worldwide PTB IECEx iaIECEx PTB 11.0037XLINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF686 KB

İlişkili Ürünler: NJ1,5-8GM-N-V1

Accessories
Female cordset single-ended M12 straight A-coded, 2-pin, PUR cable blue, NAMURfa
Female cordset single-ended M12 angled A-coded, 2-pin, PUR cable blue, NAMURfa
Mounting flange, 8 mmfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.