Fabrika Otomasyonu
Proses Otomasyonu

Fieldbus Power Hub, Basic Diagnostic Module HD2-DM-B

HD2-DM-B
  • Basic monitoring for power supply output and health
  • Plug-in Module for the FieldConnex Power Hub
  • Plug and play - no engineering required
  • For online monitoring
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 2/Class I, Div. 2
  • System state and fault indication via LEDs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Tam veri sayfasını PDF olarak indirin:


Veri sayfası alıntısı: Teknik veriler  HD2-DM-B

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V
Rated current20 mA
Power dissipationmax. 0.5 W
Indicators/operating means
LED PRI PWRgreen: on, primary bulk power supply connected
LED SEC PWRgreen: on, secondary bulk power supply connected
LED ERRred: 2 Hz flashing, power supply fault (short-circuit, undervoltage), redundancy fault
Fault signalVFC alarm 1 A, 50 V DC, normally closed
Galvanic isolation
Fieldbus segment/Fieldbus segmentfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typemotherboard specific
Core cross sectionmotherboard specific
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 70 g
Dimensions
Height106 mm
Width18 mm
Depth128 mm
Mountingmotherboard mounting
Data for application in connection with hazardous areas
CertificateTÜV 04 ATEX 2500 X
MarkingEx-Hexagon II 3 G Ex nA nC IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex nA nC IIC T4
IECEx approval
IECEx certificateIECEx TUN 13.0038X
IECEx markingEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.027242692
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC001604
ETIM 8.0EC001604
ETIM 7.0EC001604
ETIM 6.0EC001604
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: HD2-DM-B

Function

Designed as a plug-in module for the FieldConnex® Power Hub, the Basic Diagnostic Module HD2-DM-B provides basic system diagnostics. It checks for proper operation of bulk power supplies and monitors the connected trunks for overload or short-circuit conditions. All Power Hub modules are checked for proper function. On redundant power modules it indicates missmatching pairs.

The module indicates a fault condition via voltage-free contact. It provides monitoring "plug-and-play" without additional engineering. LED signals indicate a fault for easy detection.

Informative Literature: HD2-DM-B

Dil Seçeneği:
LiteratureDilDosya TipiDosya Boyutu
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB
Application Report - Fieldbus Power Supply Compatible with Process Industry ApplicationsENGPDF229 KB

Product Documentation: HD2-DM-B

Dil Seçeneği:
Safety and Security DocumentationDilDosya TipiDosya Boyutu
Instruction manualENGPDF224 KB
Manuals
Manual Basic Diagnostics HD2-DM-BENGPDF970 KB
ManualENGPDF3044 KB

Approvals: HD2-DM-B

Dil Seçeneği:
CertificatesSertifika No.DilDosya TipiDosya Boyutu
Canada FMFM 19 CA 0011XALLPDF356 KB
China SITIIAS CCC2020322310003510 (Singapore)ALLPDF1330 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe TUV Nord ATEX Category 3 GTÜV 04 ATEX 2500XALLPDF1498 KB
India PESO (India) CCOEA/P/HQ/KA/104/5874 (P507650)ALLPDF101 KB
USA FMFM 19 US 0015XALLPDF213 KB
Worldwide TUV Nord Ex nA nC IECEx nAIECEx TUN 13.0038XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0756CALLPDF1040 KB

İlişkili Ürünler: HD2-DM-B

Matching System Components
4 segments, individual modules per segment, Customizable cable connections to any PLC and PCS hosts, High-power trunk: Live work on devices in any hazardous area, Best quality, smallest size and lowest heat dissipation, For FOUNDATION Fieldbus and PROFIBUS PA, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa
4 segments, redundant, individual modules per segment, Customizable cable connections to any PLC and PCS hosts, High-power trunk: Live work on devices in any hazardous area, Best quality, smallest size and lowest heat dissipation, For FOUNDATION Fieldbus and PROFIBUS PA, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa
8 segments, redundant, individual modules per segment, Supports all PLC and PCS hosts, High-power trunk: Live work on devices in any hazardous area, Best quality, smallest size and lowest heat dissipation, For FOUNDATION Fieldbus H1, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnostics, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Matching System Components
8 segments, redundant, individual modules per segment, Customized for Invensys, FBM228, High-power trunk: Live work on devices in any hazardous area, Best quality, smallest size and lowest heat dissipation, For FOUNDATION Fieldbus H1, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

Kararlardan planlamaya, kuruluma ve devreye almaya, işletme ve bakıma kadar: Fieldbus altyapınızdan en iyi şekilde nasıl yararlanabileceğinizi keşfedin…