General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Fieldbus connection | ||
Connection | 2-wire cable, red+, black- | |
Rated voltage | max. 32 V DC | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Ambient conditions | ||
Ambient temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Mechanical specifications | ||
Core cross section | 0.75 mm2 | |
Housing | 77 mm x 22 mm | |
Degree of protection | IP67 | |
Mass | 100 g | |
Mounting | 20 mm ISO thread PG13.5 thread 1/2 NPT thread |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | DMT 01 ATEX 104 X | |
Marking | II 2G EEx d IIC T6 |
|
Temperature class | T6 for ambient temperature ≤ 60 °C T5 for ambient temperature ≤ 75 °C T4 for ambient temperature ≤ 85 °C |
|
Maximum values | ||
Rated voltage | < 253 V AC / 125 V DC | |
Operating values | ||
Rated voltage | max. 32 V | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2006 , EN 60079-1:2007 , EN 60079-26:2007 | |
International approvals | ||
IECEx approval | IECEx BVS 10.0022X | |
Approved for | Ex d IIC T6 Gb | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
F*-FT-Ex1.D.IEC are terminators for fieldbus and provide capacitance and resistance to terminate a segment according to IEC/EN 61158-2. Explosion protection is flameproof enclosure 'Ex d' for installation in Zone 1 … 2. A solid metal housing enables installation in rough environments. Housings are selectable with 20 mm ISO, 13.5 mm PG, or 0.5 in NPT threads for easy installation on outdoor fieldbus junction boxes or field devices.
For increased availability, the terminator features multiple capacitors and resistors in a network. If one capacitor fails, the basic functionality remains intact. This is detectable with the FieldConnex ® advanced diagnostic module, allowing timely maintenance.
Terminators are required at each end of the trunk line. They eliminate signal reflections at the end of the cable and convert the fieldbus signal transmitted as a current into a voltage, which is detectable by all devices.
Literature | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction Manual F*-FT -Ex1.I.IEC, F*-FT-Ex1.D.IEC | ENG | 1794 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
BVS IECEx Certificate of Conformity | IECEx BVS 10.0022X | ALL | LINK | --- |
Canada, USA CSA | CoC 1284467 | ALL | 73 KB | |
Control Drawings | ||||
Control drawing CSA / Control drawing CSA | ALL | 104 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
RSS Info Service for PANOS Updates
Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.