Temperature Trip Amplifier KFD2-GU-Ex1

KFD2-GU-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, voltage or current input
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable by PACTware
  • Sensor breakage detection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-GU-Ex1

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 35 V DC
Ripplewithin the supply tolerance
Power dissipation0.8 W
Power consumption0.8 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4, 5, 6
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
Voltage0 ... 10 V , 2 ... 10 V
Current0 ... 20 mA , 4 ... 20 mA
Load20 Ω for 20 mA; 200 kΩ for 10 V
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8, 9; output II: terminals 10, 11, 12
Output I, IIrelay
Contact loading253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Mechanical life2 x 107 switching cycles
Transfer characteristics
Resolutiontemperature: 0.0625 °C, resistance: 62.5 mΩ, voltage: 62.5 µV, current: 625 nA
Influence of supply voltage< 0.001 % of sensor input range
Input delay≤ 370 ms (rise time and energizing delay of relay)
Indicators/settings
Display elementsLEDs
Configurationvia PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateBAS 98 ATEX 7152
MarkingEx-Hexagon II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2]
CertificateTÜV 99 ATEX 1493 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval
Control drawing116-0173 (cULus)
IECEx approvalIECEx BAS 06.0022
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

Classifications

SystemClasscode
ECLASS 11.027210122
ECLASS 10.0.127210122
ECLASS 9.027210122
ECLASS 8.027210122
ECLASS 5.127210122
ETIM 8.0EC002654
ETIM 7.0EC002654
ETIM 6.0EC002654
ETIM 5.0EC001485
UNSPSC 12.132101514

Documents: KFD2-GU-Ex1

ManualsLanguageFile TypeFile Size
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB
Manual KFD2-GU-(Ex)1ENGPDF1294 KB
System Manual ENGPDF3524 KB
Handbuch KFD2-GU-(Ex)1GERPDF1193 KB
Installations- und Konfigurationsanleitung Device Type Manager (DTM)GERPDF8463 KB
SystemhandbuchGERPDF3557 KB
Instruction manuals
ИнструкцииBULPDF69 KB
Návod k poużitíCZEPDF61 KB
Instruktions manualDANPDF58 KB
Instruction manualENGPDF50 KB
KasutusjuhendESTPDF56 KB
KäyttöohjeFINPDF56 KB
Manuel d'instructionsFRAPDF97 KB
BetriebsanleitungGERPDF62 KB
Οδηγίες χρήσηςGREPDF73 KB
HandleidingHOLPDF72 KB
Instruction manual / BetriebsanleitungHRVPDF70 KB
Használati útmutatóHUNPDF71 KB
Manuale di istruzioniITAPDF93 KB
Lietošanas pamācībaLAVPDF68 KB
Instrukciju vadovasLITPDF68 KB
Instrukcja obsługiPOLPDF72 KB
Manual de instruçõesPORPDF72 KB
Manual de utilizareRONPDF71 KB
Návod na poużitieSLKPDF130 KB
Manual de instruccionesSPAPDF95 KB
ManualSWEPDF66 KB

CAD+CAE: KFD2-GU-Ex1

CADFile TypeFile Size
3-D model / 3-D-ModellSTP2510 KB
EPLAN
EPLAN Data Portal / EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ63 KB

Approvals+Certificates: KFD2-GU-Ex1

CertificatesCertificate No.File TypeFile Size
Baseefa IECEx Certificate of ConformityIECEx BAS 06.0022LINK---
Canada UL cULE106378 cUL (QUZW7)LINK---
EAC Pepperl+Fuchs EAC TP TC 020/2011EAEC N RU D-DE.PA01.B.95500/21PDF748 KB
Europe Baseefa ATEX Category (1) GDBAS 98 ATEX 7152PDF4997 KB
India PESO (India) CCOEA/P/HQ/KA/104/5908 (P513787)PDF100 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
Russia VNIIMS Pattern ApprovalDE.C.32.004.A No.29177PDF3779 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20140902 - E106378 RepRef 20011030PDF429 KB
USA ULE106378 UL (QUZW)LINK---
Control drawings
Control Drawing UL / Control Drawing UL   PDF1092 KB

Software: KFD2-GU-Ex1

Device type managersRelease InfoFile TypeFile Size
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.76ZIP32633 KB
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB

Associated Products: KFD2-GU-Ex1

Accessories
Device DTM, For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa

Function: KFD2-GU-Ex1

This isolated barrier is used for intrinsic safety applications.

The device accepts a variety of inputs including RTDs or thermocouples. The device provides a relay trip whenever it reaches a userprogrammed set point.

The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples.

A fault is indicated by LEDs acc. to NAMUR NE44 and by user-configured fault indication outputs.

The device is easily configured by the use of the PACTware configuration software.

For additional information, refer to the manual and www.pepperl-fuchs.com.