Inductive sensor NJ40-FP-SN-P4

NJ40-FP-SN-P4
  • 40 mm non-flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  NJ40-FP-SN-P4

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR with safety function
Rated operating distance40 mm
Installationnon-flush
Assured operating distance0 ... 32.4 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 100 Hz
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Functional safety related parameters
MTTFd7560 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GbIECEx PTB 11.0092X
Equipment protection level DaIECEx PTB 11.0092X
ATEX approval
Equipment protection level GbPTB 00 ATEX 2049 X
Equipment protection level DaPTB 00 ATEX 2049 X
UL approvalcULus Listed, General Purpose
KCC approval
Hazardous Location18-AV4BO-0478X
Ambient conditions
Ambient temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection type1/2 NPT terminal compartment, wire cross-section ≤ 2.5 mm2
Core cross sectionup to 2.5 mm2
Housing materialPBT/metal
Sensing facePBT
Degree of protectionIP68
Dimensions
Height40 mm
Width80 mm
Length80 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274101
ECLASS 12.027274101
ECLASS 11.027272401
ECLASS 10.0.127272401
ECLASS 9.027272401
ECLASS 8.027272401
ECLASS 5.127272401
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ40-FP-SN-P4

Documents: NJ40-FP-SN-P4

Instruction manualsFile TypeFile Size
ИнструкцииPDF181 KB
Návod k poużitíPDF174 KB
Instruktions manualPDF172 KB
Instruction manualPDF174 KB
Technical informationPDF158 KB
KasutusjuhendPDF168 KB
KäyttöohjePDF167 KB
Manuel d'instructionsPDF177 KB
BetriebsanleitungPDF175 KB
Technische InformationPDF162 KB
Οδηγίες χρήσηςPDF183 KB
HandleidingPDF174 KB
Instruction manual / BetriebsanleitungPDF172 KB
Használati útmutatóPDF176 KB
Manuale di istruzioniPDF174 KB
Lietošanas pamācībaPDF173 KB
Instrukciju vadovasPDF175 KB
Instrukcja obsługiPDF175 KB
Manual de instruçõesPDF176 KB
Manual de utilizarePDF176 KB
Návod na poużitiePDF175 KB
Navodila za uporaboPDF172 KB
Manual de instruccionesPDF176 KB
ManualPDF172 KB

CAD+CAE: NJ40-FP-SN-P4

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP105 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ69 KB

Approvals+Certificates: NJ40-FP-SN-P4

CertificatesFile TypeFile Size
Canada USA UL Ordinary LocationPDF286 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePDF9560 KB
KR KOSHA Ex ibPDF407 KB
Worldwide PTB IECEx iaLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF1307 KB
UK Declaration of Conformity (P+F)PDF1305 KB

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.