Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
MODBUS RTU gateway |
General specifications | ||
---|---|---|
AS-Interface specification | V3.0 | |
PLC-Functionality | activateable | |
Duplicate address detection | from AS-Interface slaves | |
Earth fault detection | integrated | |
EMC monitoring | integrated | |
Diagnostics function | Extended function via display | |
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTFd | 90 a at 30 °C | |
Indicators/operating means | ||
Display | Illuminated graphical LC display for addressing and error messages | |
LED AS-i ACTIVE | AS-Interface operation normal; LED green | |
LED CONFIG ERR | configuration error; LED red | |
LED PRG ENABLE | autom. programming; LED green | |
LED POWER | voltage ON; LED green | |
LED PRJ MODE | projecting mode active; LED yellow | |
LED U AS-i | AS-Interface voltage; LED green | |
LED MODBUS | MODBUS interface in operation, LED green | |
Switch SET | Selection and setting of a slave address | |
OK button | Mode selection traditional-graphical/confirmation | |
Button MODE | Mode selection PRJ-operation/save configuration/cursor | |
ESC button | Mode selection traditional-graphical/cancel | |
Electrical specifications | ||
Insulation voltage | ≥ 500 V | |
Rated operating voltage | from AS-Interface | |
Rated operating current | ≤ 180 mA from AS-Interface | |
Interface 1 | ||
Interface type | RS-485 | |
Protocol | MODBUS RTU (Remote Terminal Unit) | |
Interface 2 | ||
Interface type | RS 232, serial Diagnostic Interface |
|
Transfer rate | 19,2 kBit/s | |
Connection | ||
AS-Interface | spring terminals, removable | |
MODBUS | RS 485 interface | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Storage temperature | -15 ... 75 °C (5 ... 167 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | 420 g | |
Dimensions | ||
Height | 120 mm | |
Width | 75 mm | |
Length | 76 mm | |
Construction type | Low profile housing , Stainless steel |
System | Classcode |
---|---|
ECLASS 13.0 | 27242607 |
ECLASS 12.0 | 27242607 |
ECLASS 11.0 | 27242607 |
ECLASS 10.0.1 | 27242607 |
ECLASS 9.0 | 27242607 |
ECLASS 8.0 | 27242607 |
ECLASS 5.1 | 27242607 |
ETIM 9.0 | EC001603 |
ETIM 8.0 | EC001603 |
ETIM 7.0 | EC001603 |
ETIM 6.0 | EC001603 |
ETIM 5.0 | EC001603 |
UNSPSC 12.1 | 39121535 |
The VBG-MOD-K20-D is a MODBUS RTU gateway in accordance with AS-Interface- Specification 3.0 in IP20. The design makes it particularly suitable for use in control cabinets.
The AS-Interface data can be used in many varied ways and for a variety of purposes. All the important data are available in both binary form as well as packed and unpacked via a register. So that the AS-Interface gateways can be operated with the MODBUS slave interface by the most varied of MODBUS masters, without having to resort to expensive adaptions. The gateway is supplied from the AS-Interface cable.
The assignment of addresses and the acceptance of the set configuration is possible by means of push button keys. 7 LEDs, arranged on the front of the device, indicate the current status of the AS-Interface network.
On the AS-Interface Gateway, with graphic display, the commissioning of the AS-Interface circuit and the testing of the connected peripherals can be completely separated from the commissioning of the MODBUS and the programming. On-site operation using the graphics display and the 4 buttons enable all the functions to be depicted on the display that are covered by the other AS-Interface masters via the AS-i Control Tools software. An additional RS 232 socket provides the option of reading out data directly from the gateway, on gateway, network and function in the context of an extended on-site diagnosis.
PLC Functionality
Optionally, the gateway can be supplied with PLC functionality. Therefor you can order a code key VAZ-CTR additionally.
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Installation instructions VBG-MOD-K20-D / Montageanweisung VBG-MOD-K20-D | ALL | 676 KB | |
Manuals | |||
Manual AS-Interface 3.0 Command Interface | ENG | 3265 KB | |
Manual VBG-MOD-K20-D | ENG | 1717 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2606 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
US CA UL | E223772 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 75701 | ALL | 611 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2453B | ALL | 109 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|