AS-Interface Gateway/Safety Monitor VBG-ENX-K30-DMD-S16

VBG-ENX-K30-DMD-S16
  • Gateway and safety monitor in one housing
  • Gateway compliant with AS-Interface specification 3.0
  • Connection to Ethernet Modbus TCP/IP
  • AS-Interface safety monitor with extended range of functions
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • Memory card for configuration data
  • 2 AS-Interface networks
  • 2 safe output relays and 2 safe electronic outputs
  • Integrated switch allows line topology
  • DLR technology supports ring topology
Unit Price:  2,636.00  USD
 in stock

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of VBG-ENX-K30-DMD-S16

Product Description
EtherNet/IP + Modbus TCP Gateway with integrated safety monitor, double master for 2 AS-Interface networks
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
B10d2 E+7
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED ETHERNETethernet active; LED green
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRJ MODEprojecting mode active; LED yellow
LED U AS-iAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuitOutput circuit closed; 4 x green LEDs
Button4
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
Rated operating current≤ 300 mA off AS interface network 1
≤ 300 mA off AS interface network 2
≤ 370 mA in total
Interface 1
Interface type2 x RJ-45
ProtocolEtherNet/IP + MODBUS TCP/IP acc. to IEEE 802.3
supports device level ring protocol DLR
Transfer rate10 MBit/s / 100 MBit/s , Automatic baud rate detection
Interface 2
Interface typeRS 232, serial
Diagnostic Interface
Transfer rate19,2 kBit/s
Interface 3
Interface typeChip card slot
Input
Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Output
Safety outputmax. contact load:
Output circuits 1 and 2: 2 potential-free contacts,
3  ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
0.5  ADC-13 at 30  VDC
Connection
EthernetRJ-45
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
StandardsEN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
Approvals and certificates
UL approvalAn isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Mass800 g
Construction typeLow profile housing , Stainless steel

Documents: VBG-ENX-K30-DMD-S16

ManualsLanguageFile TypeFile Size
Manual AS-Interface 3.0 Command InterfaceENGPDF3265 KB
Manual Control III Programming in C (small PLC)ENGPDF1276 KB
Manual VBG-ENX-K30-DMD-S16*ENGPDF7792 KB
Manual Web-InterfaceENGPDF1407 KB
Handbuch AS-Interface 3.0 KommandoschnittstelleGERPDF3233 KB
Handbuch Control III Programmierung in C (Klein SPS)GERPDF1301 KB
Handbuch VBG-ENX-K30-DMD-S16*GERPDF7785 KB
Handbuch Web-InterfaceGERPDF1449 KB
Instructions, short instructions, safety information
Installation instructions VBG-ENX-K30-DMD-S16 / Montageanweisung VBG-ENX-K30-DMD-S16ALLPDF2113 KB
Technical information
Configuring a Safe Input on AS-Interface Safety at WorkENGPDF258 KB

CAD+CAE: VBG-ENX-K30-DMD-S16

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS25796 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP4057 KB

Approvals+Certificates: VBG-ENX-K30-DMD-S16

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2486CPDF314 KB
Certificates
AS-International Association AS-InterfaceZU125001PDF118 KB
EU TUV Nord Functional Safety44 205 16 000806PDF775 KB
US CA ULE223772LINK---
Worldwide AS-International Association AS-InterfaceZU93201PDF636 KB
Worldwide TUV Rheinland USA Functional Safety CertificateCU7210071201PDF980 KB

Associated Products: VBG-ENX-K30-DMD-S16

Accessories
Software for configuration of K30 Master Monitors/K31 and KE4 Safety Monitorsfa
Interface converter USB/RS 232fa
AS-Interface Product Range

Download the AS-Interface Product Overview

Get to know our full range of AS-Interface products.