Serviceline
Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827

AS-Interface gateway VBG-ENX-K20-D

VBG-ENX-K20-D
  • Gateway compliant with AS-Interface specification 3.0
  • Connection to Ethernet Modbus TCP/IP
  • Dublicate addressing detection
  • Integrated webserver
  • Earth fault detection
  • AS-Interface noise detection
  • Ethernet diagnostic interface
  • Integrated switch allows line topology
  • DLR technology supports ring topology
Unit Price:  1,521.00  USD
 in stock

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of VBG-ENX-K20-D

Product Description
EtherNet/IP + Modbus TCP Gateway
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Functional safety related parameters
MTTFd105 a at 30 °C
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED ETHERNETethernet active; LED green
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRJ MODEprojecting mode active; LED yellow
LED U AS-iAS-Interface voltage; LED green
Button4
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltagefrom AS-Interface 30 V DC
Rated operating current≤ 300 mA from AS-Interface
Interface 1
Interface type2 x RJ-45
ProtocolEtherNet/IP + MODBUS TCP/IP acc. to IEEE 802.3
supports device level ring protocol DLR
Transfer rate10 MBit/s / 100 MBit/s , Automatic baud rate detection
Interface 2
Interface typeRS 232, serial
Diagnostic Interface
Transfer rate19,2 kBit/s
Interface 3
Interface typeChip card slot
Connection
EthernetRJ-45
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
StandardsEN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
Approvals and certificates
UL approvalAn isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Mass500 g
Construction typeLow profile housing , Stainless steel

Documents: VBG-ENX-K20-D

ManualsLanguageFile TypeFile Size
Manual AS-Interface 3.0 Command InterfaceENGPDF3265 KB
Manual Control III Programming in C (small PLC)ENGPDF1276 KB
Manual VBG-ENX-K20-D*ENGPDF4732 KB
Manual Web-InterfaceENGPDF1407 KB
Handbuch AS-Interface 3.0 KommandoschnittstelleGERPDF3233 KB
Handbuch Control III Programmierung in C (Klein SPS)GERPDF1301 KB
Handbuch VBG-ENX-K20-D*GERPDF4796 KB
Handbuch Web-InterfaceGERPDF1449 KB
Instructions, short instructions, safety information
Installation instructions VBG-ENX-K20-D / Montageanweisung VBG-ENX-K20-DALLPDF1108 KB

CAD+CAE: VBG-ENX-K20-D

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS15448 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP3130 KB

Approvals+Certificates: VBG-ENX-K20-D

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2451APDF163 KB
Certificates
AS-International Association AS-InterfaceZU125001PDF118 KB
US CA ULE223772LINK---
Worldwide AS-International Association AS-InterfaceZU93201PDF636 KB

Commissioning: VBG-ENX-K20-D

Commissioning examplesLanguageFile TypeFile Size
Commissioning VBG-ENX-K20-D / Inbetriebnahme VBG-ENX-K20-DALLPDF458 KB

Associated Products: VBG-ENX-K20-D

Accessories
Full version of the AS-I Control Tools including connection cablefa
Interface converter USB/RS 232fa
AS-Interface Product Range

Download the AS-Interface Product Overview

Get to know our full range of AS-Interface products.