Type Y & Z purge and pressurization system 3004

3004
  • NFPA 496, ISA 12.4
  • Optional alarm output indicates air lock failure
  • Optional differential pressure switch for Class I, Group A-D, hazardous area locations
  • Type Y system certified for Class I, Division 1 to Division 2
  • Type Z system certified for Class I, Division 2 to nonhazardous area
  • Enclosure volume up to 7.08 m3 (250 ft3)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  3004

Product Description
3004 Series purge and pressurization system
General specifications
Series3004 Series
Hazardous environmentgas
Electrical specifications
ConnectionTerminal blocks
Output
Output I-WPS-
Output typeSwitch contacts
Contact loading120 VAC @ 15 A
Output II-WPSA-
Output typeSwitch contacts
Contact loading120/220 VAC; 24 VDC @ 10 A; 125 VDC @ 50 mA
power requirements: 24 / 120 / 240 VDC @ 3 / 4 / 11 watts
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirement80 - 120 psi (5.5 - 8.3 bar)
Safe pressureSetpoint: 0.25" (6.35 mm)
Flow rate: 0.1 - 3.5 SCFH (2.8 - 99 l /hr)
Purge flow and enclosure pressure rate30 SCFM /1800 SCFH (850 l /m / 50976 l/hr)
(With regulator set to 60 psi min. during exchange)
Operating conditions
Process conditions
Exchange time4 volume exchange rate: 1 min / 7.5 ft3 (212.4 l/m)
5 volume exchange rate: 1 min / 6.0 ft3 (169.9 l/m)
Ambient conditions
Ambient temperature-29 ... 49 °C (-20.2 ... 120.2 °F)
Mechanical specifications
Connection typeSystem supply port: 1/2" FPT
Enclosure supply port: 1/2" FPT
Enclosure reference fitting: 1/4" tube
Switch conduit port size: 1/2" FPT
MaterialRegulator body: zinc w/enamel finish
Regulator handle & bowl: polycarbonate
Enclosure pressure gauge: alum. w/enamel finish
Rapid Exchange® gauge: poly & nickel plated
Tube fitting: 316 SS forged body
Tubing: 316 SS 1/4" .035 welded
Fastener hardware: alum. & stainless steel
System face plate: 316 14 ga #3 brush SS
System mounting flange: 316 SS tumble finish
Manifold body: anodized aluminum
Manifold valves: 316 SS
Mfr. ID nameplate: silkscreen Lexan®
Mass3004-LPS-* 5.4 kg (12 lb)
3004-WPS-* 7.7 kg (17 lb)
International approvals
FM approvalType Y
LPS: Class I, Division 1, Groups A, B, C, D
WPS: Class 1, Division 1, Groups C, D
WPSA: Class I, Division 1, Groups A, B, C, D

Type Z
LPS: Class I, Division 2, Groups A, B, C, D
WPS: Class 1, Division 2, Groups C, D
WPSA: Class I, Division 2, Groups A, B, C, D
UL approval
cULusType Y
LPS: Class I, Division 1, Groups A, B, C, D
WPS: Class 1, Division 1, Groups C, D
WPSA: Class I, Division 1, Groups A, B, C, D

Type Z
LPS: Class I, Division 2, Groups A, B, C, D
WPS: Class 1, Division 2, Groups C, D
WPSA: Class I, Division 2, Groups A, B, C, D

Approvals+Certificates: 3004

CertificatesCertificate No.File TypeFile Size
Canada, USA FMCoC 3018335PDF433 KB
UL Hazardous LocationE184741 (RFPW, RFPW7)PDF288 KB

Function: 3004

The model 3004 is a Rapid Exchange® purging system that operates on a supply of compressed instrument air or inert gas.

The system regulates and monitors pressure within sealed protected enclosure(s), in order to remove and prevent flammable gas or vapor accumulations.

The system accomplishes the required volume exchanges and maintains a safe pressure. A Pepperl+Fuchs Model EPV-4 enclosure protection vent is required for proper operation.

This process reduces the hazardous (classified) area rating within protected enclosure(s), in accordance with the NEC - NFPA 70, NFPA 496, ISA 12.4.

Get to know the smartest way to ensure hazardous location protection and configure your individual purge and pressurization system!