Quantity
Free Shipping
Purchase on Account
Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Rated current | ≤ 11 mA | |
Power dissipation/power consumption | 0.3 W max. | |
Input | ||
Connection side | field side | |
Connection | terminals 4+, 5- | |
Input resistance | min. 20 MΩ | |
Transmission range | -50 ... 50 mV | |
Offset voltage/current | ≤ 5 µV / ≤ 5 nA | |
Line fault detection | 100 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 7+, 8- | |
Voltage | -50 ... 50 mV | |
Load | Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ | |
Fault signal | sensor breakage: > +100 mV (upscale), < -100 mV (downscale) | |
Output resistance | max. 3 Ω | |
Transfer characteristics | ||
Cut-off frequency | 350 Hz (-3 dB) | |
Deviation | ||
After calibration | at 20 °C (68 °F): ± 3 µV up to ± 10 mV/± 0.03 % of the span up to +50 mV/± 0.05 % of the span up to -50 mV | |
Influence of ambient temperature | ± 1 µV/K (typical ± 0.25 µV/K) | |
Absolute | < 0.25 K at 30 V voltage supply | |
Rise time | ≤ 1 ms | |
Galvanic isolation | ||
Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Protection against electrical shock | UL 61010-1 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 125 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BASEEFA 06 ATEX 0040 | |
Marking | ![]() |
|
Voltage | 5.5 V DC | |
Current | 2.4 mA | |
Power | 3.3 mW | |
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Certificate | BASEEFA 09 ATEX 0219X | |
Marking | ![]() |
|
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0334 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 06.0011 IECEx BAS 09.0103X |
|
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Manuals | Language | File Type | File Size |
---|---|---|---|
System Manual | ENG | 3524 KB | |
Systemhandbuch | GER | 3557 KB | |
Instruction leaflets | |||
Control drawing cULus / Control drawing cULus | ALL | 103 KB | |
Instruction manuals | |||
Инструкции | BUL | 69 KB | |
Návod k poużití | CZE | 61 KB | |
Instruktions manual | DAN | 58 KB | |
Instruction manual | ENG | 50 KB | |
Kasutusjuhend | EST | 56 KB | |
Käyttöohje | FIN | 56 KB | |
Manuel d'instructions | FRA | 97 KB | |
Betriebsanleitung | GER | 62 KB | |
Οδηγίες χρήσης | GRE | 73 KB | |
Handleiding | HOL | 72 KB | |
Instruction manual / Betriebsanleitung | HRV | 70 KB | |
Használati útmutató | HUN | 71 KB | |
Manuale di istruzioni | ITA | 93 KB | |
Lietošanas pamācība | LAV | 68 KB | |
Instrukciju vadovas | LIT | 68 KB | |
Instrukcja obsługi | POL | 72 KB | |
Manual de instruções | POR | 72 KB | |
Manual de utilizare | RON | 71 KB | |
Návod na poużitie | SLK | 130 KB | |
Manual de instrucciones | SPA | 95 KB | |
Manual | SWE | 66 KB |
CAD | File Type | File Size | |
---|---|---|---|
3-D model / 3-D-Modell | STP | 2510 KB | |
EPLAN | |||
EPLAN macro EDZ / EPLAN Makro EDZ | EDZ | 57 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-0774D | 83 KB | |
Certificates | |||
Australia Test Safe | ANZEx 17.3006X | 6788 KB | |
Baseefa IECEx Certificate of Conformity | IECEx BAS 09.0103X | LINK | --- |
Baseefa IECEx Certificate of Conformity | IECEx BAS 06.0011 | LINK | --- |
Belarus Pattern Approval | Nr. 11709 | 15640 KB | |
Brasil TUV Rheinland Brazil | TÜV 13.1141 | 1308 KB | |
Canada UL cUL | E106378 cUL (QVAJ7) | LINK | --- |
Canada UL cUL | E106378 cUL (QUZW7) | LINK | --- |
China NEPSI | GYJ 18.1538 | 1468 KB | |
China SITIIAS CCC Ex Certificate | 2020322316001441 (Singapore) | 950 KB | |
EAC Pepperl+Fuchs EAC TP TC 020/2011 | EAEC N RU D-DE.PA01.B.95500/21 | 748 KB | |
Europe Baseefa II (1) D I (M1) II (1) G | Baseefa 06 ATEX 0040 | 2585 KB | |
Europe Baseefa II 3 G | Baseefa 09 ATEX 0219X | 2011 KB | |
Japan TIIS | TC 18127 | 288 KB | |
Korea KOSHA | 10-AV4BO-0206 | 895 KB | |
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011 | EAEC RU C-DE.EX01.B.00102/19 | 9815 KB | |
Russia VNIIMS Pattern Approval | DE.C.32.004.A No.53706 | 4041 KB | |
USA UL | E106378 UL (QUZW) | LINK | --- |
USA UL | E106378 UL (QVAJ) | LINK | --- |
Control drawings | |||
Control drawing UL / Control drawing UL | 52 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
This isolated barrier is used for intrinsic safety applications.
It transfers low voltage signals from load cells, strain gauges, operational amplifiers, and inductive oscillation sensors located in hazardous areas to safe areas.
The input voltage of the terminals 4 and 5 is transferred to the terminals 7 and 8.
The input, output, and power supply are galvanically isolated from each other. Upscale or downscale lead breakage monitoring is selectable via switches located on the front panel of the device.
Note: This unit requires three minutes after power-up to reach the accuracy cited in the technical data.