Serviceline
Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827

PROFIBUS Power Hub, Gateway Module HD2-GTR-4PA

HD2-GTR-4PA
  • PROFIBUS DP V1 / For 4 segments PA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • Optional redundant configuration
  • Installation in Zone 2/Class I, Div. 2
  • Up to 12 Mbit/s, auto adapting
  • For redundant and non-redundant masters
  • Supports Flying Redundancy (FR)
  • Cyclic/acyclic data exchange
Unit Price:  2,551.00  USD
 Please contact the Serviceline for exact delivery estimation

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of HD2-GTR-4PA

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC
Rated current160 ... 90 mA
Power dissipation3 W
Fieldbus interface
PROFIBUS DP
Connection9-pin Sub-D socket
ProtocolPROFIBUS DP V1
Indicators/operating means
LED Seg 1...4red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error
LED PWRgreen: Power on
LED DP/ERRred 2 Hz flashing: DP error ; red: Hardware error
LED Red.yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available
Galvanic isolation
CH/PROFIBUS DPfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
PROFIBUS DP/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
CH/CHfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Low voltage
Directive 73/23/EECEN 50178 (identical to EN 62103)
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Housing width40 mm
Housing height106 mm
Housing depth128 mm
Degree of protectionIP20
Mass250 g
Mountingmotherboard mounting , mounting in any orientation
Data for application in connection with hazardous areas
Statement of conformityTÜV 04 ATEX 2500 X
Group, category, type of protection, temperature classEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approvalCoC 3024816, CoC 3024816C
Approved forClass I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4
IECEx approvalIECEx TUN 13.0038X
Approved forEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038

Approvals+Certificates: HD2-GTR-4PA

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2267APDF85 KB
Certificates
Canada FMCoC 3024816CPDF54 KB
DNV GL MarineA-14038PDF45 KB
Europe TUV Nord ATEX Category 3 GTÜV 04 ATEX 2500XPDF1498 KB
USA FMCoC 3024816PDF54 KB
Worldwide TUV Nord Ex nA nC IECEx nAIECEx TUN 13.0038XLINK---

Software: HD2-GTR-4PA

DriversRelease InfoFile TypeFile Size
GSD file / GSD-DateiV1.5ZIP6 KB
Software Tools
GSD converter for transparent gateways / GSD-Konverter für transparente GatewaysV1.3ZIP793 KB

Associated Products: HD2-GTR-4PA

Matching system components
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectablepa
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnosticspa
Accessories
User interface for PROFIBUS components, Simple access to measurements, diagnostic and configuration data, Supports any FDT/DTM hostpa

Download Quick Select Guide Process Interfaces

The Quick Select Product Guide for interface technology, FieldConnex®, and remote I/O connection technologies will help you select the right technology and systems when designing plants.