Terminal and Junction Boxes Ex e / Ex i with Return Flange, Stainless Steel FXLS***.T

FXLS***.T
  • Stainless Steel enclosure
  • Return Flange Sealing
  • Ex e, Ex ia and Ex tb certified
  • 21 enclosure size options
  • Customizable configuration of terminals, cable entries and cable gland types as per specification
  • Up to 4 gland plates
  • Installation in Zone 1, Zone 2, Zone 21 and Zone 22
  • Wide range of accessories available

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of FXLS***.T

Electrical specifications
Operating voltage1100 V AC max. , depending on size and certification
Operating current350 A max. , depending on size and certification
Mechanical specifications
Enclosure coverfully detachable , concealed hinges
Cover fixingM6 stainless steel hexagon head screws
Cover sealone piece closed cell neoprene
Degree of protectionIP66 , FXLS11* and FXLS11*D*: IP54
Cable entrythru-holes direct through body
or via gland plate
Terminal assembly
Number of railssee PDF data sheet
Terminal typeStandard see PDF data sheet, other terminal types optional
Number of terminals per railsee PDF data sheet
Material
Enclosure1.5 mm 316L, (1.4404) stainless steel
Gland plate3 mm 316L, (1.4404) stainless steel
Finishelectropolished
Masssee PDF data sheet
Dimensionssee PDF data sheet
GroundingM10 internal/external brass grounding bolt
M6 internal stainless steel grounding bolt welded to lid
M6 internal stainless steel grounding bolt welded to body
Ambient conditions
Ambient temperature-40 ... 40 °C (-40 ... 104 °F) , optional -50 ... 120 °C (-58 ... 248 °F)
Data for application in connection with hazardous areas
EU-Type Examination CertificateCML 16 ATEX 3008X
MarkingEx-Hexagon II 2 GD
Ex eb IIC T* Gb, Ex db eb IIC T* Gb, Ex tb IIIC T** Db or
Ex ia IIC T* Gb, Ex tb IIIC T** Db or
Ex eb IIC T* Gb, Ex ia IIC T* Gb, Ex tb IIIC T** Db
T6/T80 °C @ Ta +40 °C
T5/T95 °C @ Ta +55 °C
T4/T125 °C @ Ta +85 °C
T3/T160 °C @ Ta +120 °C
Maximum power dissipationsee PDF data sheet
International approvals
IECEx approvalIECEx CML 16.0007X
INMETROTÜV 13.1665X
EAC approvalTC RU C-DE.GB06.B.00567
Conformity
Degree of protectionEN60529
CE marking0102
General information
Ordering informationThis terminal box will be delivered completely configured and assembled ready for use. For configuration details please contact customer service.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessoriessee PDF data sheet

Documents: FXLS***.T

Instructions, short instructions, safety informationLanguageFile TypeFile Size
Brief Instructions Terminal Boxes Series FXL*.T / XL*.T / SL*.T (notified body: CML)ENGPDF196 KB
Brief Instructions XL/FXL/SL terminal boxesENGPDF702 KB
Brief Instructions XL/FXL/SL terminal boxesFRAPDF704 KB
Kurzanleitung XL/FXL/SL-KlemmenkästenGERPDF706 KB
Brief Instructions XL/FXL/SL terminal boxesRUSPDF758 KB

Approvals+Certificates: FXLS***.T

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3238APDF80 KB
Certificates
CML IECEx Certificate of ConformityIECEx CML 16.0007XLINK---
Europe CML II 2GD ATEXCML 16 ATEX3008XPDF424 KB
Europe Sira II 2GD ATEXSira 99 ATEX 3199PDF117 KB
Sira IECEx Certificate of ConformityIECEx SIR 06.0074LINK---
Russia Kazakhstan Belarus NANIO "CCVE"TC RU C-DE.GB06.B.00567PDF10239 KB

Ready for Shipment in 5 Days: Custom Terminal Boxes and Control Units

When ordering within Europe, your custom Ex e terminal box or local control unit is ready for shipment in just five days! Use our online tools to quickly configure your individual solution …

Spotlight: Six Questions for Herbert Schober

Pepperl+Fuchs provides customers with customized control units, terminal boxes as well as disconnect switches for hazardous areas, including certification, within just five days. Herbert Schober tells us more about this part of the electrical explosion protection equipment portfolio.