Trip amplifier 2/209

2/209
  • 4-channel
  • Input 0/4 mA ... 20 mA
  • 4 relay contact outputs
  • Programmable
  • Simple operation via front buttons
  • Lead monitoring
  • Galvanic isolation between input, power supply and contact output
  • With computational function SIL3
  • LCD display
  • Self-monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  2/209

Product Description
Trip amplifier with 1-4 trip values
General specifications
Signal typeAnalog input
Supply
Connectionz2+, z4-, z6 (PE)
Rated voltage18 ... 30 V DC
18 ... 26.4 V AC 48 ... 62 Hz
Power consumption2 W / 2.5 VA
Input
ConnectionInput A I: d32+, z32-
Input A II: d30+, z30-
Input A III: d28+, z28-
Input A IV: d26+, z26-
Input B I: b32+, z32-
Input B II:b30+, z30-
Input B III: b28+, z28-
Input B IV: b26+, z26-
Input resistance50 Ω (mA)
10 kΩ (V)
Current range0/4 ... 20 mA (0/1 ... 5 V)
Output
ConnectionOutput I: z10, d12, d10
Output II: d14, z14, z12
Output III: z16, d18, d16
Output IV: d20, z20, z18
Relay
Switching voltage50 V
Switching current2 A AC/DC
Switching power500 VA / 60 W
Mechanical life50 Mio. cycles
Electrical life0.5 Mio. cycles
Response time> 20 ms (variable)
Transfer characteristics
Temperature influence< 0.1 %/10 K
Indicators/settings
Display elementsLED 1: trip value 1
LED 2: trip value 2
LED 3: trip value 3
LED 4: trip value 4
LED green: Power on
Configurationvia RS-485 interface at the front side
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Ambient conditions
Ambient temperature-10 ... 60 °C (14 ... 140 °F)
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Mechanical specifications
Mass300 g
Dimensions22 x 143 x 193 mm (0.9 x 5.6 x 7.6 inch)
Height143 mm
Width22 mm
Length193 mm
Construction typeEurocard 100 x 160 mm (3.9 x 6.3 inch) acc. to DIN 41494, front panel 4TE, mountable in 19 inch rack
Certificates and approvals
SIL classificationSIL3 (IEC 61508)
TÜV Rheinland 968/EL 292-03/08
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210122
ECLASS 12.027210122
ECLASS 11.027210122
ECLASS 10.0.127210122
ECLASS 9.027210122
ECLASS 8.027210122
ECLASS 5.127210122
ETIM 9.0EC002654
ETIM 8.0EC002654
ETIM 7.0EC002654
ETIM 6.0EC002654
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: 2/209

Function

The programmable self-monitoring device is used to line monitor external set points, gradients, ratios or min/max selections.

Set points are programmable via front push-buttons or PC.

Input, power supply and relay contact output are galvanically isolated.

Product Documentation: 2/209

Language Selection:
ManualsLanguageFile TypeFile Size
Instruction Manual Trip amplifier 2/209ENGPDF2082 KB

Approvals: 2/209

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Europe TUV Rheinland Functional Safety968/EL 292.06/13ALLPDF279 KB

Software: 2/209

Language Selection:
Software ToolsRelease InfoFile TypeFile Size
Parameterization Software / Parametriersoftware07/2009ZIP41730 KB