| General specifications |
| Switching element function | DC NO |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | ≤ 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indication | all direction LED, yellow |
| Functional safety related parameters |
| MTTFd | 2090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
| Connection type | cable PUR , 10 m |
| Cable version | PA |
| Core cross-section | 0.14 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Protection degree | IP67 |