Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBB10-30GKK-WS

NBB10-30GKK-WS
  • Basic series

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of NBB10-30GKK-WS

General specifications
Switching functionNormally open (NO)
Output typeTwo-wire
Rated operating distance10 mm
Installationflush
Output polarityAC
Assured operating distance0 ... 8.1 mm
Reduction factor rAl 0.33
Reduction factor rCu 0.28
Reduction factor r304 0.82
Nominal ratings
Operating voltage20 ... 250 V
Switching frequency0 ... 20 Hz
Hysteresistyp. 5 %
Short-circuit protectionno
Voltage drop≤ 8 V
Momentary current
(20 ms, 0.1 Hz)
0 ... 1600 mA
Operating current1.5 ... 200 mA
No-load supply current≤ 1.7 mA
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typeterminal compartment
Core cross-sectionup to 2.5 mm2
Housing materialPBT
Sensing facePBT
Housing diameter30 mm
Degree of protectionIP67
Note1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V
Safety fuse ≤ 0.8 A (quick-blow) according to IEC 60127-2 Sheet 1
Recommendation: after a short circuit, check that the device is functioning correctly.

Documents: NBB10-30GKK-WS

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF191 KB
EinbaubedingungenGERPDF194 KB
warunki montażuPOLPDF245 KB
Условия монтажаRUSPDF274 KB

CAD+CAE: NBB10-30GKK-WS

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS266 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP188 KB

Approvals+Certificates: NBB10-30GKK-WS

CertificatesCertificate No.File TypeFile Size
China CQC CCC2010010305385286PDF2601 KB
US CA CSA1007121 (LR96321-2)PDF101 KB
US CA UL General PurposeE87056LINK---