| General specifications |
| Signal type | Digital Output |
| Supply |
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 20 ... 30 V DC |
| Power loss | < 2 W supply voltage 30 V, all outputs loaded with 600 mA |
| Input |
| Connection | Terminals 7+, 8+, 9+, 10+, 15- |
| Input current | approx. 2 mA at 24 V DC |
| Signal level | 0-signal: 0 ... 5 V DC 1-signal: 16 ... 30 V |
| Output |
| Open loop voltage | 24 V DC |
| Connection | terminals 1+, 2+, 3+, 4+, 5-, 6- |
| Switching frequency | 1 kHz |
| Output rated operating current | 600 mA , sustained short-circuit proof and overload-proof |
| Line fault detection | lead breakage: ≤ 4 mA |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
| Conformity |
| Electromagnetic compatibility | NE 21:2006 |
| Protection degree | IEC 60529:2001 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Protection degree | IP20 |
| Mass | approx. 100 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |