Temperature control unit with LED display
KT-LED-96-2R-24VDC





    Serviceline Information


    • Galvanic isolation
    • Polarity reversal protected
    • Protection degree IP65 (front only)

    Datasheet as PDF in following languages:


    Technical Data: KT-LED-96-2R-24VDC

    Product Description
    Temperature control unit with LED display and 24 VDC supply voltage
    General specifications
    Data storage106 storage cycles or 10 years, EEPROM
    Programmingkeypad-driven menu
    Functional safety related parameters
    MTTFd350 a
    Mission Time (TM)10 a
    Diagnostic Coverage (DC)0 %
    Indicators/operating means
    Type5-digit 7-segment LED display, red
    Display valuedigit height 14.2 mm
    Display interval-19999 ... 99999
    with suppression of leading zeros
    Decimal point0 to max 1 fractional digit
    Resetmanually or external
    Electrical specifications
    Fusing250 mA/T
    Operating voltage10 ... 30 V DC galvanically isolated
    Power consumptionmax. 2 W
    Input 1
    Input typemeasurement for thermoelements B, E, J, K, N, R, S, T
    Resolution0.1 °C (0.1 °F)
    Compensation (reference junction CJC)internal or external (programmable)
    Input 2
    Input typeMeasurement input for resistance thermometer type Pt100, Pt1000
    Resolution0.1 °C (0.1 °F)
    Connection2-, 3- und 4-Leiter-Anschlusstechnik, programmierbar
    Current800 µA at Pt100
    80 µA at Pt1000
    Input 3
    Input typeMeasurement input for resistance measurement
    Resistor0 ... 400 Ω
    0 ... 4000 Ω
    Resolution14 Bit
    Connection2-, 3- und 4-Leiter-Anschlusstechnik, programmierbar
    Current800 µA at 400 Ω
    80 µA at 4000 Ω
    Input 4
    Input typeMillivolt measurement input with automatic zero adjustment
    Voltage range0 ... 100 mV DC
    -100 ... 100 mV DC
    Resolution14 Bit
    Input resistancemin. 2 MΩ
    Measuring frequencyapprox. 1 measurement per sec.
    Input 5
    Input typeDigital inputs,
    Input MPI: Display hold or reset limit value latch
    Input KEY: Keyboard lock
    Signal voltage
    High4 ... 30 V DC
    Low0 ... 2 V DC
    Minimum pulse durationmin. 5 ms
    Output 1
    Output type2 limit value outputs, relay with floating changeover contact
    Switching voltage250 V AC / 300 V DC
    Switching currentmax. 3 A AC/DC
    min. 30 mA DC
    Switch power50 W / 2000 VA
    Output 2
    Output typeAuxiliary power output for signal converter/measurement sensor,
    galvanically isolated
    Output voltage10 V DC ± 3 %, 30 mA,
    Compliance with standards and directives
    Directive conformity
    EMC Directive 2004/108/ECEN 61000-6-2:2005
    Standard conformity
    Emitted interferenceDIN EN 55011:2009, Class B
    Ambient conditions
    Ambient temperature-20 ... 65 °C (-4 ... 149 °F)
    Storage temperature-40 ... 85 °C (-40 ... 185 °F)
    Relative humidity≤ 75 % (noncondensing)
    Mechanical specifications
    Protection degreeIP65 (front)
    Massapprox. 212 g
    Dimensions96 mm x 48 mm x 90.7 mm

    Documents: KT-LED-96-2R-24VDC

    ManualsLanguageFile TypeFile Size
    Manual KT-LED-96-2R-*ENGPDF2053 KB
    Manual KT-LED-96-2R-*FRAPDF1992 KB
    Handbuch KT-LED-96-2R-*GERPDF2099 KB
    Manual KT-LED-96-2R-*SPAPDF1998 KB