Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
EtherNet/IP and Modbus IO-Link master with 4 x IO-Link Class A and 4 x IO-Link Class B ports |
General specifications | ||
---|---|---|
UL File Number | E360395 | |
Indicators/operating means | ||
LED indication | see manual | |
Rotary switch | Setting the IP address | |
Electrical specifications | ||
Rated operating voltage | 20 ... 30 V DC | |
General information | M12, L-coded | |
Protection class | PELV or Limited Voltage power supply required | |
Nominal voltage | 24 V DC | |
Current consumption | typ. 120 mA | |
Current loading capacity | Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 6.5 A per module (Class A) Total current: max. 10.4 A per module (Class B) |
|
Galvanic isolation | between US and UA | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | M12, D-coded | |
Protocol | EtherNet/IP + Modbus TCP + OPC UA + MQTT
Modbus max PDI: 33 times / sec OPC UA max PDI update rate: 20 times / sec MQTT max PDI update rate: 10 times / sec |
|
Transfer rate | 10/100 Mbps | |
Inputs/Outputs | ||
Number/Type | 4 x IO-Link Class B (X1 – X4) and 4 x IO-Link Class A (X5 – X8) Configurable as: Class 2, , PELV or Limited Voltage power supply required max. 12 digital inputs and digital outputs short-circuit protected |
|
Sensor supply | Ports 1 - 8: max. 500 mA per port via L+ (pin 1) | |
Actuator supply | Port 1: max. 3.5A via 2L+ (pin 2) Ports 2-4: max. 2.3A via 2L+ (pin 2) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2 , EN 61000-6-4 | |
RoHS | EN IEC 63000:2018 | |
Standard conformity | ||
Degree of protection | EN 60529 | |
Fieldbus standard | IEC 61131-2 | |
Electrical safety | CSA C22.2 No. 61010-1-12 UL 61010-1, IEC 61010-2-201 |
|
Emitted interference | EN 61000-6-4, FCC Part 15 Subpart B, ICES-001, AS/NZS CISPR 11 | |
Noise immunity | EN 61000-6-2 , EN 61131-2 , EN 61131-9 | |
Shock resistance | EN 60068-2-27 | |
Ambient conditions | ||
Operating temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 2000 m | |
Shock and impact resistance | 15g, 11ms, half-sine | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded |
|
Material | ||
Housing | Molded Polyamide 66 | |
Mass | 454 g | |
Tightening torque, fastening screws | 8 Nm | |
Tightening torque, cable gland | 0.6 Nm | |
Dimensions | 65 mm 29.8 mm 212 mm | |
Height | 212 mm | |
Width | 65 mm | |
Length | 30 mm | |
Mounting | Machine or panel |
System | Classcode |
---|---|
ECLASS 13.0 | 27242608 |
ECLASS 12.0 | 27242608 |
ECLASS 11.0 | 27242608 |
ECLASS 10.0.1 | 27242608 |
ECLASS 9.0 | 27242608 |
ECLASS 8.0 | 27242608 |
ECLASS 5.1 | 27242608 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The module is an EtherNet/IP fieldbus module with 4 type A IO-Link master ports and 4 type B IO-Link master ports according to IO-Link standard V1.1. The fieldbus module serves as an interface between the controller of an EtherNet/IP fieldbus system and IO-Link devices in the field level. The integrated web server and IODD interpreter enabling complete configuration of the fieldbus module and attached IO-Link devices without the need for special software tools. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured. The module is capable of storing all configuration enabling stand-alone usage without a higher level PLC. MutliLink simultaneously provides data access via different communication protocols like EtherNet/IP, Modbus/TCP, OPC UA and MQTT to multiple controllers. An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A. The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug. Status information for each channel is displayed via LEDs as a diagnostic function.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Industrial Communication - IO-Link Master - CNC Machines | ENG | 757 KB | |
Application Report - Seamless Communication from the Sensor to the Cloud | ENG | 171 KB | |
Product Overview - IO-Link-Master with OPC UA Interface | ENG | 1504 KB |
Manuals | Language | File Type | File Size |
---|---|---|---|
Class B Port Supporting Information | ENG | 2968 KB | |
ICE2/ICE3 MQTT | ENG | 880 KB | |
Manual | ENG | 27177 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 6572 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA UL UL | E360395 | ALL | LINK | --- |
ODVA Ethernet/IP | 11916.02 | ALL | 128 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-4275E | ALL | 111 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-5810A | ALL | 108 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
EtherNet/IP EDS (v1.6_1.54) and Firmware (v1.6.54) files for ICE2 / EtherNet/IP-EDS (v1.6_1.54) und Firmware (v1.6.54) Dateien für ICE2 | August 2024 | ZIP | 13683 KB |
AOI (Add On Instruction) files for RSLogix 5000 / AOI (Add On Instruction) Dateien für RSLogix 5000 | 07/2019 | ZIP | 2070 KB |
Software Tools | |||
Ethernet/IP Tag Description Generator. Assists the user in visualizing the input, output, status and event data. Also can generate a CSV file for upload in to RSLogix/Studio 5000. / Software Tool_a | 01/2021 | ZIP | 26974 KB |
PortVision DX v6.02 / PortVision DX v6.02 | 2020-08 | ZIP | 29584 KB |
Simplified AOIs (Add On Instructions) for Rockwell Automation Studio 5000. Read and Write a single parameter on an ICE1, ICE2, ICE11 or Allen Bradley IO-Link masters / Inbetriebnahmedatei_a | 2.0 Dec 19, 2023 | ZIP | 56091 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|