Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
G20 IO-Link module for 16 freely configurable digital inputs/outputs |
General specifications | ||
---|---|---|
MTBF | 149 a | |
Indicators/operating means | ||
LED green | <--, -->: IO1..8 / IO9..16 bank indication | |
LED yellow/red | IO1 ... IO16: inputs/outputs status, IO-Link status | |
Electrical specifications | ||
Operating voltage | 18 ... 30 V DC, PELV Current limitation of the supply max. 4 A |
|
No-load supply current | ≤ 25 mA | |
Operating current | max. 4 A | |
Interface | ||
Interface type | IO-Link | |
IO-Link revision | 1.1 | |
Device profile | Identification and Diagnosis - I&D | |
Process data | Inputs 3 Byte - Input signals 16 Bit - diagnosis signals 5 Bit Outputs 2 Byte - Output signals 16 Bit |
|
Vendor ID | 1 (0x0001) | |
Device ID | 985345 (0x0F0901) | |
Data transfer rate | COM3 (230.4 kbits/s) | |
Min. cycle time | 1 ms |
|
SIO mode support | no | |
Compatible master port type | Class A |
|
Input | ||
Number/Type | 16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16) | |
Supply | from IO-Link | |
Current loading capacity | 200 mA , overload and short-circuit protected | |
Input current | ≤ 5 mA (limited internally) | |
Switching point | Type 3 according to IEC 61131-2 | |
Output | ||
Number/Type | 16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof | |
Supply | from IO-Link | |
Voltage | ≥ (UB - 1.5 V) | |
Current | 200 mA per output | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 EN 55011:2016 |
|
Conformity | ||
Communication interface | IEC 61131-9:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 61131-9:2013 | |
Input | EN 61131-2:2007 | |
Communication interface | IEC 61131-9 / IO-Link V1.1.3 | |
Emitted interference | EN 61000-6-4:2007 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 | |
Ambient conditions | ||
Ambient temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Storage temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Relative humidity | 85 % non-condensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 5000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | IO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded) Female connector: LF type or similar IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded) Mating connector: LM type or similar |
|
Mass | 310 g | |
Dimensions | ||
Height | 27.5 mm | |
Width | 131.5 mm | |
Length | 54 mm | |
Mounting | 2 clips with ∅ 8 mm drill hole The module must be secured to a solid, continuous surface using the two lugs |
|
Cable length | 1 m (IO-Link) 0.2 m (IO1/2, IO15/16), 0.3 m (IO3/4, IO13/14) 0.4 m (IO5/6, IO11/12); 0.5 m (IO7/8, IO9/10) max. 10 m |
System | Classcode |
---|---|
ECLASS 13.0 | 27242602 |
ECLASS 12.0 | 27242602 |
ECLASS 11.0 | 27242602 |
ECLASS 10.0.1 | 27242602 |
ECLASS 9.0 | 27242602 |
ECLASS 8.0 | 27242602 |
ECLASS 5.1 | 27242602 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The ICA-16IO-G20-IO-P16 is an IO-Link field module with 16 freely configurable digital inputs/outputs. The compact housing can be mounted directly in support profiles or cable ducts.
The module and the inputs and outputs are supplied with voltage via IO-Link.
The inputs and outputs are connected via cable outlets with 4-pin M8 sockets. IO-Link is connected via a cable outlet with 4-pin M12 connector.
The current switching state or an overload of the inputs or outputs is indicated via the IN or OUT LEDs.
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual | ENG | 635 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
IO-Link Manufacturer Declaration | CERT-7194 | ALL | 173 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-7463_ENG | ENG | 196 KB | |
UK Declaration of Conformity (P+F) | TDOC-7464_ENG | ENG | 171 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
IODD / IODD | V1.01.001 / 2023-11-21 | ZIP | 228 KB |
Software Tools | |||
IO-Link Offline Parameterization Tool / IO-Link Offline-Parametriertool | V1.00.006 / 2022-07-10 | ZIP | 96138 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.