Select Your Country
KCD2-SLD-Ex1.1245 Solenoid Driver
Key Benefits at a Glance
- 1-channel isolated barrier
- 24 V DC supply (bus or loop powered)
- Output 45 mA at 12 V DC
- Line fault transparency (LFT)
- Test pulse immunity
- Housing width 12.5 mm
- Up to SIL 3 acc. to IEC/EN 61508
Show more






Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- EN
- DE
- ES
- FR
- PL
Technical data of KCD2-SLD-Ex1.1245
| Signal type | Digital Output |
| Safety Integrity Level (SIL) | SIL 3 | |
| Systematic capability (SC) | SC 3 |
| Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
| Rated voltage | Ur | 19 ... 30 V DC loop powered |
| Input current | 75 mA at 24 V , 270 Ω load | |
| Power dissipation | 1.3 W at 24 V , 270 Ω load |
| Connection side | control side | |
| Connection | terminals 5+, 6- | |
| Test pulse length | max. 2 ms from DO card | |
| Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC | |
| Rated current | Ir | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
| Inrush current | < 200 mA , 10 ms loop powered |
| Connection side | field side | |||||||||||||
| Connection | terminals 1+, 2- | |||||||||||||
| Internal resistor | Ri | 240 Ω | ||||||||||||
| Current | Ie | typ. 45 mA | ||||||||||||
| Voltage | Ue | typ. 12 V | ||||||||||||
| Current limit | Imax | 50 mA | ||||||||||||
| Open loop voltage | Us | typ. 24.6 V | ||||||||||||
| Load | nominal 0.05 ... 18 kΩ , valid range for line fault detection (LFD) | |||||||||||||
| Output II | fault signal | |||||||||||||
| ||||||||||||||
| Line fault detection | ||||||||||||||
| ||||||||||||||
| Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output II/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff |
| Display elements | LEDs | |
| Control elements | DIP switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
| Degree of protection | IEC 60529:2013 | |
| Protection against electrical shock | EN 61010-1:2010 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | EXA 17 ATEX 0002 X | ||||||||||||||||
| |||||||||||||||||
| Supply | |||||||||||||||||
| |||||||||||||||||
| Input | |||||||||||||||||
| |||||||||||||||||
| Collective error message | |||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| FM approval | ||||||||
| ||||||||
| UL approval | E106378 | |||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |