Select Your Country
6500-01-*-PNO-LNO Purge+Pressurization System
6500 series purge and pressurization system in the Ex pxb and Ex pyb types of protection
Key Benefits at a Glance
- Automatic purge and pressurization system for most applications
- User-friendly, easy programming
- LCD screen for operation status and LEDs for quick visual system identification
- HART communication via RS-485 with PACTware
- Maximum enclosure size 12.75 cubic meters
- Compact design with panel mounts or direct mounts available
- Universal power 20 to 30 VDC / 100 to 250 VAC. 50 to 60 HZ
- Pressure, temperature, dilution control and monitoring
- Up to SIL 2 acc. to IEC/EN 61508
Show more






Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- EN
- DE
Technical data of 6500-01-*-PNO-LNO
| Operating mode | user programmable | |
| Series | 6500 | |
| System | Ex pxb Purge , Ex pyb Purge | |
| Number of volume exchanges | 5 to 19 | |
| Hazardous environment | gas, dust, gas and dust |
| Safety Integrity Level (SIL) | SIL 2 |
| Rated voltage | Ur | 100 ... 240 V AC, 48 ... 62 Hz / 0.2 A 20 ... 30 V DC |
| Connection | EPCU: Terminal blocks and grounding screw UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters Input type: intrinsically safe |
| Input I | Voltage free contact or namur proximity sensor | ||||
| |||||
| Input II | (1) 2-wire, PT100 RTD | ||||
| |||||
| Output I | AUX | |||||||||||||
| ||||||||||||||
| Output II | Enclosure | |||||||||||||
| ||||||||||||||
| Output III | Digital valve When used with the 6500-MAN-DV-01, intrinsically safe Internal resistance 280 Ω | |||||||||||||
| Output IV | Proportional valve When used with the 6500-MAN-PV-01, intrinsically safe Current: 4 to 20 mA Max. load: 300 Ω | |||||||||||||
| Communication | HART via RS485 (PACTware available) | |||||||||||||
| Display elements | 2x20 LCD for configuration, monitoring, and status of the 6500 system with back light and contrast selection. Capacitive touch buttons | |
| LED indication | Safe pressure: Blue - safe pressure is achieved Enclosure power: Green - power on; Red - power off Rapid exchange: Blue - purging is running System bypass: Yellow - bypass is activated Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6500 series system fault Key: green - a button on the capacitive touch display has been activated. Momentary indication |
| Protective gas supply | instrument grade air or inert gas | |
| Pressure requirement | For 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120 psig) regulated For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated Note: max. pressure will depend on the vent model used. | |
| Safe pressure | Gas: 0.82 mbar (0.33 in wc) Dust: 0.82 mbar (0.33 in wc) Gas+Dust: 0.82 mbar (0.33 in wc) | |
| Valve flows | Standard vent series: EPV-6500-*-01, 03, 05 Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm). Minimum and maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. Continuous (Dilution) vent series: EPV-6500-*-07, 08 Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading. Maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. |
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Relative humidity | 5 ... 85 %, non-condensing | |
| Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes | |
| Impact resistance | 30 g, 11 ms, all axes |
| Connection type | See mounting in 6500 manual and cable gland requirements | ||||||||||
| Cable gland | Cable gland requirement: cable glands are not included. Customer can supply their own approved glands or use one of the 6500-CBLG-... cable gland kits. I.S.cable glands: requires (5) M12 approved cable glands Power cable glands: requires (2) M16 and (2) M12 approved cable glands | ||||||||||
| Degree of protection | IP66 | ||||||||||
| Material | UIC display: Makrolon FI cover and A380 Aluminum anodized casing Housing: 316L stainless steel Hardware: 316L stainless steel | ||||||||||
| Mass | approx. 5 kg (11.0 lbs) | ||||||||||
| Dimensions | 6500-01-EXT1: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7") 6500-01-PM01: 150 x 150 x 185 mm (5.9" x 5.9" x 7.3") 6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7"), UIC: 150 x 150 x 45 mm (5.9" x 5.9" x 1.8") | ||||||||||
| |||||||||||
| Certificate | DEMKO 16 ATEX 1640X | ||||
| Directive conformity | |||||
| |||||
| IECEx approval | IECEx UL 16.0003X |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Related Pages
Are you looking for more information? Feel free to learn more on our related pages.