VAA-4E4A-KE-ZE/R ASi Input/Output Module

KE switch cabinet module, 4 inputs (PNP) and 4 relay outputs

Key Benefits at a Glance

  • Housing with removable, mechanical and color coded terminals
  • Communication monitoring
  • Inputs for 2- and 3-wire sensors
  • Isolated relay output
  • Addressing jack
  • Selectable supply to the sensors: External or from the module
  • Function display for bus, internal sensor supply, inputs, and outputs

Show more

Contact us for estimated delivery.4 694,00 ZAR Net price—your individual price will be shown during checkout process.
Product Compliance: Europe – CE
Product Compliance: USA - cULus
AS-Interface® interface
Note

All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

EN
  • EN
  • DE
  • FR
  • ZH

Technical data of VAA-4E4A-KE-ZE/R

Node typeStandard node
AS-Interface specificationV2.1
Required gateway specification≥ V2.0
ProfileS-7.0
IO code7
ID code0
ID1 codeF
ID2 codeE
UL File NumberE106378
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow
Auxiliary voltage (input)UEXT12 ... 30 V DC PELV
Rated operating voltageUe26.5 ... 31.6 V from AS-Interface
Rated operating currentIe≤ 35 mA (no sensors)/max. 210 mA
Surge protectionO1 ... O4: Over voltage category II
UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity≤ 150 mA, overload- and short-circuit protected (INT)
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Signal delay< 2 ms (input/AS-Interface)
Number/Type4 relay outputs, normally open
Supplynone
Nominal load
Per contact2 A / 30 V DC (acc. UL max. 24 V DC); 2 A / 253 V AC
Per module8 A
Control circuit≤ 8 mA per relay (from AS-Interface)
Switching delay< 10 ms (AS-Interface/contact)
Usage categoryDC-13 and AC-14
Switching
Mechanical5 x 106
Electrical0.2 x 106 (250 V AC, 2 A, cos φ = 0.4)
Overload protectionfuse unit 2 A required in the load current circuit
Input/Outputsafe isolation, rated insulation voltage 300 V AC
Input/AS-InterfaceSwitch position INT: None Switch position EXT: reinforced insulation, rated insulation voltage 66 V DC
Output/Outputbasic insulation, rated insulation voltage 300 V AC
Output/AS-Interfacesafe isolation, rated insulation voltage 300 V AC
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61326:2003
Low voltage
Directive 73/23/EECEN 60947-1:2007
Galvanic isolationEN 60664-1:2007
Electromagnetic compatibilityNAMUR NE 21: 1998-08
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
AS-InterfaceEN 62026-2:2013
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree2
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass170 g
Dimensions
Height99 mm
Width22.5 mm
Length102 mm
MountingDIN mounting rail
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm
General Notes