Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Solenoid Driver KFD2-SLD-Ex1.13100

KFD2-SLD-Ex1.13100
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Logic input
  • Output 100 mA at 13 V DC
  • Alternating outputs for the operation of solenoids with 2 coils
  • High output power for IIB gas group
  • Line fault transparency (LFT)
  • Test pulse immunity
  • Up to SIL 3 acc. to IEC 61508

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-SLD-Ex1.13100

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
loop powered
Input current115 mA at 24 V , 130 Ω load
Power dissipation1.5 W at 24 V , 130 Ω load
Input
Connection sidecontrol side
Connectionchannel 1: terminals 7+, 8- channel 2: terminals 10+, 11-
Input currentapprox. 6 mA at 24 V DC
Signal level1-signal: 15 ... 30 V DC
0-signal: 0 ... 5 V DC
Output
Connection sidefield side
Connectionchannel 1: terminals 1+, 2-, 3
channel 2: terminals 4+, 5-, 6-
Internal resistorapprox. 64 Ω
Currenttyp. 100 mA
Voltage≥ 13 V
Current limit105 mA
Open loop voltagetyp. 19.2 V
Loadnominal 0.08 ... 1 kΩ
Switching frequencymax. 2 Hz
Energized/De-energized delay30 ms / 30 ms
Line fault detectionsignal at short-circuit RB < 30 Ω, lead breakage RB > 10 kΩ ,
test current < 4 mA pulsing (20 ms On, 200 ms Off)
Galvanic isolation
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Input/inputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 200 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateEXA 17 ATEX 0076X
MarkingEx-Hexagon II 3(1)G Ex ec [ia IIB Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Voltage22.2 V
Current360 mA
Power1990 mW
Supply
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Galvanic isolation
Output/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V
Output/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012
International approvals
IECEx approvalIECEx EXA 17.0019X
Approved forEx ec [ia IIB Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)

Documents: KFD2-SLD-Ex1.13100

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF440 KB
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Funktionale SicherheitGERPDF441 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction manuals
ИнструкцииBULPDF137 KB
Návod k poużitíCZEPDF131 KB
Instruktions manualDANPDF0 KB
Instruction manualENGPDF135 KB
KasutusjuhendESTPDF126 KB
KäyttöohjeFINPDF126 KB
Manuel d'instructionsFRAPDF132 KB
BetriebsanleitungGERPDF136 KB
Οδηγίες χρήσηςGREPDF138 KB
HandleidingHOLPDF0 KB
Instruction manual / BetriebsanleitungHRVPDF129 KB
Használati útmutatóHUNPDF131 KB
Manuale di istruzioniITAPDF130 KB
Lietošanas pamācībaLAVPDF0 KB
Instrukciju vadovasLITPDF130 KB
Instrukcja obsługiPOLPDF132 KB
Manual de instruçõesPORPDF131 KB
Manual de utilizareRONPDF130 KB
Návod na poużitieSLKPDF130 KB
Navodila za uporaboSLVPDF128 KB
Manual de instruccionesSPAPDF131 KB
ManualSWEPDF127 KB
Technical information
Application Guideline Solenoid DriversENGPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteineGERPDF737 KB

Approvals+Certificates: KFD2-SLD-Ex1.13100

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3755PDF88 KB
Certificates
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
EXA [Ex ia] Ex ec IECEx Certificate of ConformityIECEx EXA 17.0019XLINK---
Europe EXA ATEXEXA 17 ATEX 0076XPDF2059 KB
Russia EAC Kazakhstan BelarusTC RU C-DE.AA71.B.00291PDF2516 KB
Worldwide TUV Nord Functional Safety Certificate8000479841PDF2219 KB

Associated Products: KFD2-SLD-Ex1.13100

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa