Potentiometer Converter KFD2-PT2-Ex1-5

KFD2-PT2-Ex1-5
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Potentiometer input
  • Current output 4 mA ... 20 mA
  • Lead resistance compensation adjustment
  • Accuracy 0.05 %
  • Up to SIL 2 acc. to IEC 61508

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-PT2-Ex1-5

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power dissipation1 W
Power consumption1.3 W
Input
Connection sidefield side
Connectionterminals 4-, 5-, 3+, 2+, 1+
Potentiometer
Types of measuring3-, 4-, 5-wire technology
Nominal resistance800 Ω to 100 kΩ
Supply voltageapprox. 4.7 V
Lead resistance5 % of the potentiometer resistance (adjustable)
Output
Connection sidecontrol side
Connectionterminals 7-, 8+
Current output4 ... 20 mA, load ≤1 kΩ
Transfer characteristics
Accuracy0.05 %
Deviation
Linearity± 10 µA
Influence of ambient temperature≤ 1 µA/K
Rise time10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Control elementspotentiometer
Configurationvia potentiometer
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 120 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateBAS 00 ATEX 7171
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C)
Voltage10.4 V DC
Current31.4 mA
Power82 mW
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateTÜV 02 ATEX 1797 X
MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0129
UL approval
Control drawing116-0173 (cULus)
CSA approval
Control drawing116-0132
IECEx approvalIECEx BAS 10.0060
IECEx BAS 10.0061X
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex nA II T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD2-PT2-Ex1-5

ManualsLanguageFile TypeFile Size
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF69 KB
Návod k poużitíCZEPDF61 KB
Instruktions manualDANPDF58 KB
Instruction manualENGPDF50 KB
KasutusjuhendESTPDF56 KB
KäyttöohjeFINPDF56 KB
Manuel d'instructionsFRAPDF97 KB
BetriebsanleitungGERPDF62 KB
Οδηγίες χρήσηςGREPDF73 KB
HandleidingHOLPDF72 KB
Instruction manual / BetriebsanleitungHRVPDF70 KB
Használati útmutatóHUNPDF71 KB
Manuale di istruzioniITAPDF93 KB
Lietošanas pamācībaLAVPDF68 KB
Instrukciju vadovasLITPDF68 KB
Instrukcja obsługiPOLPDF72 KB
Manual de instruçõesPORPDF72 KB
Manual de utilizareRONPDF71 KB
Návod na poużitieSLKPDF130 KB
Manual de instruccionesSPAPDF95 KB
ManualSWEPDF66 KB

Approvals+Certificates: KFD2-PT2-Ex1-5

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0055BPDF144 KB
Certificates
Australia Test SafeANZEx 17.3006XPDF6788 KB
Baseefa IECEx Certificate of ConformityIECEx BAS 10.0060LINK---
Baseefa Type n IECEx Certificate of ConformityIECEx BAS 10.0061XLINK---
Belarus Pattern ApprovalNr. 11709PDF15640 KB
Canada CSACoC 1404404PDF133 KB
Canada UL cULE106378 cUL (QUZW7)LINK---
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe Baseefa II (1) D ATEX Category (M1) ATEX Category (1) D ATEX Category (1) GBAS 00 ATEX 7171PDF3144 KB
Europe TUV Nord ATEX Category 3 GTÜV 02 ATEX 1797XPDF1285 KB
Japan TIISTC 16186PDF497 KB
Pepperl+Fuchs Functional Safety AssessmentFS-0058PF-20APDF81 KB
Russia Belarus EAC Kazakhstan NANIO "CCVE"TC RU C-IT.GB05.B.00718PDF2731 KB
Russia VNIIMS Pattern ApprovalDE.C.34.004.A No.56757PDF976 KB
USA FMCoC 1Z2A1.AXPDF78 KB
USA FMFM Listed (Approval Guide)LINK---
USA ULE106378 UL (QUZW)LINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF58 KB