Product Description | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 9+, 10- or power feed module/Power Rail | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Power dissipation/power consumption | ≤ 0.98 W / 0.98 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4 | |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
|
Measuring current | approx. 200 µA with RTD | |
Types of measuring | 2-, 3-, 4-wire connection | |
Lead resistance | max. 50 Ω per line | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
|
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection) | |
Voltage | selectable within the range -100 ... 100 mV | |
Input resistance | ≥ 1 MΩ (-100 ... 100 mV) | |
Output | ||
Connection side | control side | |
Connection | terminal 5: source (-), terminal 6: source (+), terminal 7: sink(-), terminal 8: sink (+) | |
Output | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Fault signal | downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43) | |
Source | load 0 ... 550 Ω open-circuit voltage ≤ 18 V |
|
Sink | Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V, series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 5)/0.0215 Ω. |
|
Transfer characteristics | ||
Deviation | ||
After calibration | Pt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1.5 K (1.7 K for types R and S)) this includes ± 1.3 K error of the cold junction compensation mV: ± (50 µV + 0.1 % of span) potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes errors due to lead resistance)) |
|
Influence of ambient temperature | deviation of CJC included: Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*) mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*) potentiometer: ± 0.006 % of span/K ΔTamb*) *) ΔTamb = ambient temperature change referenced to 23 °C (296 K) |
|
Influence of supply voltage | < 0.01 % of span | |
Influence of load | ≤ 0.001 % of output value per 100 Ω | |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
|
Galvanic isolation | ||
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
|
Indicators/settings | ||
Display elements | LEDs | |
Configuration | via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
|
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BASEEFA 13 ATEX 0102 X | |
Marking | ![]() ![]() ![]() |
|
Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Inputs | terminals 1, 2, 3, 4 | |
Voltage | 9 V | |
Current | 13.1 mA | |
Power | 30 mW | |
Analog outputs, power supply, collective error | ||
Maximum safe voltage | 250 V (Attention! This is not the rated voltage.) | |
Interface | ||
Maximum safe voltage | 250 V (Attention! The rated voltage is lower.), RS 232 | |
Certificate | BASEEFA 13 ATEX 0103 X | |
Marking | ![]() |
|
Galvanic isolation | ||
Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0379 (cULus) | |
IECEx approval | IECEx BAS 13.0057X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
CAD | File Type | File Size | |
---|---|---|---|
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 458 KB | |
Dimension drawing 3-D in IGS format / Abmessungszeichnung 3-D im IGS-Format | IGS | 217 KB | |
Dimension drawing 3-D in STP format / Abmessungszeichnung 3-D im STP-Format | STP | 179 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-0164C | 58 KB | |
Certificates | |||
Belarus Pattern Approval | Nr. 11709 | 15640 KB | |
Canada UL cUL | E106378 cUL (QUZW7) | LINK | --- |
Canada UL cUL | E106378 cUL (QVAJ7) | LINK | --- |
China SITIIAS CCC Ex Certificate | 2020322316001219 (Singapore) | 1255 KB | |
EAC EAC TP TC 020/2011 | TC RU C-DE.MH04.B.00397 | 680 KB | |
Europe Baseefa II (1) G Group I (M1) II (1) D ATEX Category (1) GD | Baseefa 13 ATEX 0102X | 557 KB | |
Europe Baseefa II 3 G ATEX Category 3 G | Baseefa 13 ATEX 0103X | 457 KB | |
IECEx Certificate of Conformity | IECEx BAS 13.0057X | LINK | --- |
India PESO (India) CCOE | A/P/HQ/KA/104/5699 (P444518) | 707 KB | |
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011 | EAEC RU C-DE.EX01.B.00102/19 | 9815 KB | |
Russia VNIIMS | DE.C.34.004.A No.64324/1 | 10397 KB | |
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC 20130723 - E106378 RepRef 20130720 | 256 KB | |
USA UL | E106378 UL (QVAJ) | LINK | --- |
USA UL | E106378 UL (QUZW) | LINK | --- |
Control drawings | |||
Control Drawing UL / Control Drawing UL | 46 KB |
Device type managers | Release Info | File Type | File Size |
---|---|---|---|
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 2 | 1.4.110.76 | ZIP | 32633 KB |
Software Tools | |||
PACTware 4.1 SP6 / PACTware 4.1 SP6 | 4.1.0.53 | ZIP | 43327 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
This isolated barrier is used for intrinsic safety applications.
The device converts RTD input signals or thermocouple input signals in the hazardous area to 0/4 mA ... 20mA signals in the safe area.
The removable terminal block KC-CJC-** is available for thermocouples when internal cold junction compensation is desired.
A fault is indicated by an LED and by user-configured fault indication outputs.
If the device is operated via Power Rail, additionally a collective error message is available.
The device is easily configured by the use of the PACTware configuration software.
For additional information, refer to the manual and www.pepperl-fuchs.com.