Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

SMART Transmitter Power Supplies KFD2-STC4-1.2O

KFD2-STC4-1.2O
  • 1-channel
  • 2 galvanically isolated outputs
  • 24 V DC supply voltage
  • EMC acc. to NAMUR NE 21
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  KFD2-STC4-1.2O

Product Description
Input 0/4 mA ... 20 mA
Output 0/4 mA ... 20 mA
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power dissipation1.6 W
Power consumptionapprox. 2.5 W
Input
Connectionterminals 1+, 2-, 3
Input signal0/4 ... 20 mA
Input resistancemax. 50 Ω terminals 2-, 3
Available voltage≥ 15.7 V at 20 mA terminals 1+, 3
Ripple≤ 50 mVss at 20 mA
Output
Connectionterminals 7-, 8+,9; 10-, 11+,12
Load0 ... 550 Ω
Output signal0/4 ... 20 mA (overload > 25 mA)
Ripplemax. 50 µA eff
Transfer characteristics
Deviationat 20 °C (68 °F), 0/4 ... 20 mA
≤ ± 20 µA incl. calibration, linearity, hysteresis, loads and supply voltage fluctuations
Influence of ambient temperature≤ 20 ppm/K
Frequency rangeinput in output: bandwidth with 1 mApp signal 0 ... 7.5 kHz (-3 dB)
output in input: band width with 1 Vss signal 0.3 ... 7.5 kHz (-3 dB)
Rise time20 µs
De-energized delay20 µs
Galvanic isolation
Input/OutputBasic insulation according to EN 50178, rated insulation voltage 253 Veff
Input/power supplyBasic insulation according to EN 50178, rated insulation voltage 253 Veff
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch)
Height118 mm
Width20 mm
Length115 mm

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-STC4-1.2O

Datasheet: KFD2-STC4-1.2O

DatasheetFile TypeFile Size
Datasheet KFD2-STC4-1.2OPDF253 KB
Datenblatt KFD2-STC4-1.2OPDF255 KB

Documents: KFD2-STC4-1.2O

ManualsFile TypeFile Size
System ManualPDF3694 KB
SystemhandbuchPDF3706 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.