Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Current/Voltage Trip Value KFD2-GS-1.2W

KFD2-GS-1.2W
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Current and voltage input
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable via DIP switches and potentiometer
  • Terminal blocks with test sockets

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-GS-1.2W

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Rated current< 50 mA
Power consumption< 1.5 W
Input
Connection sidefield side
Measurement rangeterminals 1+, 3-: voltage 0/1 ... 5 V, load ≥ 50 kΩ or voltage 0/2 ... 10 V, load ≥ 100 kΩ
terminals 2+, 3-: current 0/4 ... 20 mA ; load ≤ 50 Ω
Output
Connection sidecontrol side
Output I, IIterminals 7, 8, 9; 10, 11, 12
Contact loading250 V AC / 4 A / cos φ > 0.7; 40 V DC / 2 A resistive load
Output IIIdevice configuration : terminals 4, 5, 6
Transfer characteristics
Deviation≤ 1 %
Influence of ambient temperature0.01 % / K of adjusted trip value
Input delay200 ms
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
potentiometer
Configurationvia DIP switches
via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Degree of protectionIEC 60529
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 120 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD2-GS-1.2W

ManualsLanguageFile TypeFile Size
Manual Signal Conditioners K-SystemENGPDF694 KB
Handbuch Signaltrenner K-SystemGERPDF698 KB
Manual Signal Conditioners K-SystemRUSPDF3736 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF53 KB
Návod k poużitíCZEPDF47 KB
Instruktions manualDANPDF47 KB
Instruction manualENGPDF41 KB
KasutusjuhendESTPDF44 KB
KäyttöohjeFINPDF44 KB
Manuel d'instructionsFRAPDF79 KB
BetriebsanleitungGERPDF43 KB
Οδηγίες χρήσηςGREPDF55 KB
HandleidingHOLPDF56 KB
Instruction manual / BetriebsanleitungHRVPDF55 KB
Használati útmutatóHUNPDF55 KB
Manuale di istruzioniITAPDF77 KB
Lietošanas pamācībaLAVPDF54 KB
Instrukciju vadovasLITPDF55 KB
Instrukcja obsługiPOLPDF57 KB
Manual de instruçõesPORPDF56 KB
Manual de utilizareRONPDF56 KB
Návod na poużitieSLKPDF115 KB
Manual de instruccionesSPAPDF79 KB
ManualSWEPDF53 KB

Approvals+Certificates: KFD2-GS-1.2W

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2362APDF373 KB