Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Temperature Repeater KCD2-RR-Ex1

KCD2-RR-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  KCD2-RR-Ex1

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Rated current< 20 mA
Power consumption0.35 W (24 V and 1 mA sense current)
Input
Connectionterminals 1, 2, 3, 4
Line fault detectionyes , at Pt100
Lead resistance≤ 10 % of resistance value
Transmission range0 ... 10 mA
Available voltage9 V
Line fault detection50 nA
Output
Connectionterminals 5-, 7-, 6+, 8+
Current0 ... 10 mA
Available voltage0 ... 7 V
Fault signal< 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1 mA)
Transfer characteristics
DeviationIm ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable).
Influence of ambient temperatureIm ≥ 1 mA, Rm ≥ 100 Ω: 0.01 %/K in the range -20 ... +60 °C (-4 ... 140 °F)
Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm
Rise timesignal response time ≤ 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 Ω and Im < 5mA: < 5ms
response to application of Im: Rm > 30 Ω and Im < 5mA: < 10ms
response to application of Im: Rm > 18 Ω and Im < 5mA: < 20ms
Galvanic isolation
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Height124 mm
Width12.5 mm
Length114 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 10 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage12.4 V
Current17.4 mA
Power54 mW
Supply
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 10 ATEX 0062X , observe statement of conformity
MarkingEx-Hexagon II 3G Ex nA II T4 Gc [device in zone 2]
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0129 (cFMus)
UL approval
Control drawing116-0332 (cULus)
IECEx approvalIECEx BAS 10.0024
IECEx BAS 10.0025X
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KCD2-RR-Ex1

This isolated barrier is used for intrinsic safety applications.

It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas.

A 2-, 3-, or 4-wire technique is available depending on the required accuracy.

The input card of the control system measures the same load as if it were connected directly to the resistance in a hazardous area.

Datasheet: KCD2-RR-Ex1

DatasheetFile TypeFile Size
Datasheet KCD2-RR-Ex1PDF439 KB
Fiche de données KCD2-RR-Ex1PDF448 KB
Datenblatt KCD2-RR-Ex1PDF434 KB
Datasheet KCD2-RR-Ex1PDF473 KB
Hoja de datos KCD2-RR-Ex1PDF421 KB

Documents: KCD2-RR-Ex1

ManualsFile TypeFile Size
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction leaflets
Operating instructions KCD2-RR-Ex1 / Betriebsanleitung KCD2-RR-Ex1PDF761 KB
Instruction manuals
ИнструкцииPDF69 KB
Návod k poużitíPDF61 KB
Instruktions manualPDF58 KB
Instruction manualPDF50 KB
KasutusjuhendPDF56 KB
KäyttöohjePDF56 KB
Manuel d'instructionsPDF97 KB
BetriebsanleitungPDF62 KB
Οδηγίες χρήσηςPDF73 KB
HandleidingPDF72 KB
Instruction manual / BetriebsanleitungPDF70 KB
Használati útmutatóPDF71 KB
Manuale di istruzioniPDF93 KB
Lietošanas pamācībaPDF68 KB
Instrukciju vadovasPDF68 KB
Instrukcja obsługiPDF72 KB
Manual de instruçõesPDF72 KB
Manual de utilizarePDF71 KB
Návod na poużitiePDF130 KB
Manual de instruccionesPDF95 KB
ManualPDF66 KB

CAD+CAE: KCD2-RR-Ex1

CADFile TypeFile Size
CAD 2-D / CAD 2-DZIP458 KB
CAD 3-D / CAD 3-DSTP179 KB
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ106 KB

Approvals+Certificates: KCD2-RR-Ex1

CertificatesFile TypeFile Size
Canada FMPDF321 KB
Canada UL cULLINK---
Europe Baseefa II (1) D I (M1) II (1) GPDF3083 KB
Europe Baseefa II 3 G ATEX Category 3 GPDF2465 KB
Pepperl+Fuchs Functional Safety AssessmentPDF133 KB
USA FMPDF165 KB
USA ULLINK---
Control Drawings
Control drawing FM / Control drawing FMPDF58 KB

Associated Products: KCD2-RR-Ex1

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
2-pin, Fully insulated, For connectors with 5.0 mm or 5.08 mm pitchpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces greenpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.