Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Multiplexer Master KFD2-HMM-16

KFD2-HMM-16
  • 16-channel
  • 24 V DC supply (Power Rail)
  • HART field device input (revision 5 to 7)
  • Up to 15 KFD0-HMS-16 slave units can be connected
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-HMM-16

Product Description
HART Multiplexer Master
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionterminals 17+, 18-
Rated voltage20 ... 32 V DC typical at 100 mA
Power consumptionmax. 3 W
HART signal channels (non-intrinsically safe)
ConformityHART field device input (revision 5 to 7)
Connection26-pin flat cable for analog connections
14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16
Leakage current< 3 µA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistorexternal 230 ... 500 Ω standard (up to 1000 Ω possible)
Output voltage≥ 400 mV ss (with the terminator resistance specified above)
Output resistance100 Ω or smaller, capacitive coupling
Input impedanceaccording to HART specification
Input voltage range0.08 ... 4 V ss ; typ. ± 5.2 V as local reference
Interface
Transfer rate9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user)
TypeRS-485 , 2-wire multidrop
Address selectionOne of 31 possible addresses selectable per DIL switch (4 ... 8)
Indicators/settings
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 250 g
Dimensions40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) (W x H x D) , housing type C1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 07 CERT 1143 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242692
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001597
UNSPSC 12.139121008

Documents: KFD2-HMM-16

ManualsLanguageFile TypeFile Size
Manual KFD*-HM*-16ENGPDF8323 KB
Handbuch KFD*-HM*-16GERPDF8276 KB
Instruction manuals
ИнструкцииBULPDF61 KB
Návod k poużitíCZEPDF55 KB
Instruktions manualDANPDF54 KB
Instruction manualENGPDF47 KB
KasutusjuhendESTPDF51 KB
KäyttöohjeFINPDF51 KB
Manuel d'instructionsFRAPDF88 KB
BetriebsanleitungGERPDF50 KB
Οδηγίες χρήσηςGREPDF63 KB
HandleidingHOLPDF64 KB
Instruction manual / BetriebsanleitungHRVPDF64 KB
Használati útmutatóHUNPDF64 KB
Manuale di istruzioniITAPDF85 KB
Lietošanas pamācībaLAVPDF62 KB
Instrukciju vadovasLITPDF62 KB
Instrukcja obsługiPOLPDF65 KB
Manual de instruçõesPORPDF65 KB
Manual de utilizareRONPDF65 KB
Návod na poużitieSLKPDF123 KB
Manual de instruccionesSPAPDF87 KB
ManualSWEPDF61 KB

Approvals+Certificates: KFD2-HMM-16

CertificatesCertificate No.File TypeFile Size
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF 07 CERT 1143 XPDF209 KB
exida Functional Safety AssessmentP+F 02/4-11 R006PDF348 KB
Declaration of Conformity
UK-Declaration of conformity / UK-KonformitätserklärungDOC-5294APDF1037 KB

Software: KFD2-HMM-16

Device type managers (DTM)Release InfoFile TypeFile Size
DTM Collection HART-Multiplexer / DTM Collection HART-Multiplexer2.0.1.208ZIP13306 KB
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB

Associated Products: KFD2-HMM-16

Matching System Components

Connection board for K-System HART Multiplexer, 16-channel, Interface for series connection or parallel connection, Integrated, switchable 220 Ω resistor, Connection via screw terminalspa

16-channel, No external power required, HART field device input (revision 5 to 7), Used with HART Multiplexer Master KFD2-HMM-16, Up to SIL 3 acc. to IEC/EN 61508pa
System board for Schneider Electric, Tricon series by Triconex, HART Termination Board (ETP) for Tricon AO module, For 8-channel AO card 3805E, 8-channel, Field side: pluggable screw terminals, green, Control side: ELCO socket, 56-pinpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, HART Termination Board (ETP) for Tricon v10 AI module, For 16-channel AI cards 3700, 3700A, 3703E and 3721, 16-channel, Field side: pluggable screw terminals, green, Control side: ELCO socket, 56-pinpa
Matching System Components
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Device DTM, For HART multiplexers, Communication DTMpa
Communication DTM, Frame application, like e. g. PACTware, must be installed separatelypa
Human machine interface, For HiDMux2700, For KFD2-HMM-16/KFD0-HMS-16pa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa

Function: KFD2-HMM-16

This HART Multiplexer Master operates up to 256 analog field instruments. The built-in slave unit in the HART master operates the first 16 field instruments. If more than 16 field instruments are required, up to 15 additional HART Multiplexer Slaves KFD0-HMS-16 can be connected.

The slave units are connected to the master with a 14-pin flat cable. The connector for the ribbon cable is found on the same housing side as the connectors for the interface and the power supply.

The analog signals are separately linked to a termination board via a 26-pin flat cable for each unit. Sixteen leads are reserved for the HART signal of the analog measurement circuits. The remaining 10 leads are sent to ground.

This unit is designed with removable terminals and can be connected to the Power Rail.

Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.