Serviceline Industrial Sensors
Serviceline Explosion Protection

Standstill and Rotational Direction Monitor KFD2-SR2-Ex2.W.SM

KFD2-SR2-Ex2.W.SM
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Selectable frequency trip values
  • 2 relay contact outputs
  • Start-up override
  • Selectable mode of operation
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-SR2-Ex2.W.SM

General specifications
Signal typeDigital Input
Programmingvia DIP switch and programmable
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 1.5 W
Input
Connection sidefield side
ConnectionInput I: terminals 1+, 2+, 3- ;
Input II: terminals 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Control inputsensor power supply approx. 8.2 V, impedance 1.2 kΩ
Pulse duration> 200 µs for standstill monitoring,
> 250 µs for rotation direction detecion
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Trip valuefor standstill monitoring:
0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz
adjustable via DIP switch (S1 and S2)
Transfer characteristics
Accuracy5 % (S3 = I), 30 % (S3 = II)
Start-up override5 seconds or 20 seconds, programmable
Frequency range≤ 2 kHz
Rotation direction detection90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2080
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Voltage10.5 V
Current13 mA
Power34 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Fault indication output
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
CertificateTÜV 99 ATEX 1493 X
MarkingEx-Hexagon II 3G Ex ec nC IIC T4 Gc
Output
Contact loading50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
FM approval
FM certificateFM19US0207X
Control drawing116-0035
UL approvalE106378
Control drawing116-0145
CSA approval
Control drawing116-0047
IECEx approval
IECEx certificateIECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)

Approvals+Certificates: KFD2-SR2-Ex2.W.SM

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0170CPDF93 KB
Certificates
Australia Test SafeANZEx 17.3006XPDF6788 KB
Brasil TUV Rheinland Brazil Ex nA nCTÜV 13.1124XPDF1353 KB
Canada CSACoC 1029981 CPDF201 KB
Canada UL cULE106378 cUL (QUZW7)LINK---
DNV GL MarineTAA00001WXPDF77 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2080PDF2272 KB
Europe TUV II 3 GTÜV 99 ATEX 1493XPDF756 KB
Korea KOSHA09-AV4BO-0222-1PDF346 KB
PESO (India) CCOEA/P/HQ/KA/104/5674 (P440216)PDF968 KB
PTB IECEx Certificate of ConformityIECEx PTB 11.0034LINK---
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
South Africa MASCMASC MS/17-0863PDF262 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20160608 - E106378 RepRef 19970520PDF246 KB
USA FMFM 19 US 0207XPDF350 KB
USA ULE106378 UL (QUZW)LINK---
Worldwide TUV Nord IECEx Certificate of ConformityIECEx TUN 19.0013XLINK---
exida Functional Safety AssessmentP+F 04/03-14 R017PDF148 KB
Control drawings
Control Drawing CSA / Control Drawing CSA   PDF159 KB
Control Drawing FM / Control Drawing FM   PDF130 KB
Control Drawing UL / Control Drawing UL   PDF165 KB

Associated Products: KFD2-SR2-Ex2.W.SM

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa

Function: KFD2-SR2-Ex2.W.SM

This isolated barrier is used for intrinsic safety applications.

This device is a standstill monitor that accepts input frequency pulses and triggers an output when the frequency drops below a preselected limit value.

Two start-up override values are available. This unit can also be used to determine rotation direction.

During an error condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44.

The device has LED status indicators for direction of rotation detection, limit detection, supply, and hardware faults.

The device is easily configured by the use of DIP switches.

If the device is operated via Power Rail, additionally a collective error message is available.

For additional information, refer to www.pepperl-fuchs.com.