Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

SMART Current Driver HiD2038

HiD2038
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Current output up to 650 Ω load
  • SMART I/P and valve positioners
  • Line fault detection (LFD)
  • Accuracy 0.1%
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiD2038

General specifications
Signal typeAnalog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 40 mA at 24 V
Power dissipation≤ 1 W at 20 mA and 500 Ω load
Power consumption≤ 1 W
Input
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Input signal4 ... 20 mA , limited to approx. 30 mA
Input voltageopen loop voltage of the control system ≤ 30 V
Voltage dropapprox. 6 V at 20 mA
Input resistancefield wiring open circuit : > 100 kΩ
field wiring < 50 Ω : > 100 kΩ when using terminals 5a, 5b; 1a, 1b
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
SL2: 5b(-), 7a(+); 1b(-), 3b(+) (no short circuit detection)
Voltage≥ 13 V at 20 mA
Current4 ... 20 mA
Load100 ... 650 Ω , for terminals 1a, 1b; 5a, 5b
0 ... 550 Ω , for terminals 1b, 3b; 5b, 7a
Ripple20 mV rms
Line fault detectionbreakage, load > 100 kΩ, short-circuit, load < 50 Ω
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Deviationat 20 °C (68 °F), 4 ... 20 mA
< 0.1 % of full scale, incl. non-linearity and hysteresis
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % ≤ 10 ms
Galvanic isolation
Input/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/inputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
EN 61326-3-2:2018
For further information see system description.
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Height114 mm
Width18 mm
Depth130 mm
Mountingon termination board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateDEMKO 20 ATEX 2378 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia, Ex iaD
Voltage25.2 V
Current93 mA
Power585.3 mW
Internal capacitance1.05 nF
Internal inductance0
Supply
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage250 V rms (Attention! The rated voltage can be lower.)
CertificateDEMKO 20 ATEX 2379 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
International approvals
UL approvalE106378
Control drawing116-0475 (cULus)
IECEx approval
IECEx certificateIECEx ULD 20.0012X
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2038

Function

This isolated barrier is used for intrinsic safety applications.

The device repeats the input signal from a control system to drive HART I/P converters, electrical valves, and positioners located in a hazardous area.

Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.

Current transferred across the DC/DC converter is repeated at the terminals 5a, 5b (1a, 1b). The terminals 5b, 7a (1b, 3b) are used when no short-circuit detection is required.

An open or short field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system.

Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions are monitored via a Fault Indication Board.

This device mounts on a HiD Termination Board.

Product Documentation: HiD2038

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF170 KB
Functional Safety ManualENGPDF1969 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiD2038

Language Selection:
CADLanguageFile TypeFile Size
CAD 2-D / CAD 2-DALLZIP16364 KB

Approvals: HiD2038

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada, USA UL Hazardous Location Certificate of Compliance cULus UL E106378CoC E106378 RepRef E106378-20200610ALLPDF236 KB
China SITIIAS CCC Ex Certificate2021322316003750 (Singapore)ALLPDF1058 KB
Europe DEMKO ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GDEMKO 20 ATEX 2378XALLPDF57 KB
Europe DEMKO ATEX Category 3 GDEMKO 20 ATEX 2379XALLPDF50 KB
South Africa MASCMASC MS/23-8231XALLPDF662 KB
UL IECEx Certificate of ConformityIECEx ULD 20.0012XALLLINK---
Worldwide TUV Rheinland Functional Safety CertificateTÜV-Rheinland 968/FSP 2066.00/20ALLPDF650 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF27 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4802AALLPDF81 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.