SMART Current Driver KFD2-SCD2-1.LK

KFD2-SCD2-1.LK
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Current output up to 700 Ω load
  • HART I/P and valve positioner
  • Line fault detection (LFD)
  • Accuracy 0.05 %
  • Terminal blocks with test sockets
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  KFD2-SCD2-1.LK

General specifications
Signal typeAnalog output
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power dissipation0.8 W at 20 mA into 10 V (equivalent to 500 Ω) load
Power consumption1 W at 20 mA
Input
Connectionterminals 7-, 8+, (9+)
Voltage dropapprox. 4 V or internal resistance 200 Ω at 20 mA
Input resistanceapprox. 100 kΩ, when an open circuit is applied to the field circuit
Current4 ... 20 mA limited to approx. 25 mA
Output
Connectionterminals 1+, 2-, (3-)
Voltage≥ 14 V at 20 mA
Current4 ... 20 mA
Load100 ... 700 Ω
Transfer characteristics
Deviation
After calibrationat 20 °C (68 °F): ≤ 10 µA incl. non-linearity, calibration, hysteresis, supply and load changes
Influence of ambient temperature≤ 1 µA/K
Rise time< 100 µs , 10 ... 90 % step change
Galvanic isolation
Input/Outputbasic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Input/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/power supplybasic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Height124 mm
Width20 mm
Length115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SCD2-1.LK

Datasheet: KFD2-SCD2-1.LK

DatasheetFile TypeFile Size
Datasheet KFD2-SCD2-1.LKPDF387 KB
Fiche de données KFD2-SCD2-1.LKPDF395 KB
Datenblatt KFD2-SCD2-1.LKPDF388 KB
Datasheet KFD2-SCD2-1.LKPDF409 KB
Hoja de datos KFD2-SCD2-1.LKPDF393 KB

Documents: KFD2-SCD2-1.LK

ManualsFile TypeFile Size
System ManualPDF3694 KB
SystemhandbuchPDF3706 KB
Instruction manuals
ИнструкцииPDF53 KB
Návod k poużitíPDF47 KB
Instruktions manualPDF47 KB
Instruction manualPDF41 KB
KasutusjuhendPDF44 KB
KäyttöohjePDF44 KB
Manuel d'instructionsPDF79 KB
BetriebsanleitungPDF43 KB
Οδηγίες χρήσηςPDF55 KB
HandleidingPDF56 KB
Instruction manual / BetriebsanleitungPDF55 KB
Használati útmutatóPDF55 KB
Manuale di istruzioniPDF77 KB
Lietošanas pamācībaPDF54 KB
Instrukciju vadovasPDF55 KB
Instrukcja obsługiPDF57 KB
Manual de instruçõesPDF56 KB
Manual de utilizarePDF56 KB
Návod na poużitiePDF115 KB
Manual de instruccionesPDF79 KB
ManualPDF53 KB

CAD+CAE: KFD2-SCD2-1.LK

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP3048 KB

Approvals+Certificates: KFD2-SCD2-1.LK

Declaration of ConformityFile TypeFile Size
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF311 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.