Serviceline Industrial Sensors
Serviceline Explosion Protection

SMART Universal Barrier HiC2441

HiC2441
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Analog input, digital input,
    analog output, digital output
  • No configuration required, device is self-adapting
  • HART transparency
  • Low power dissipation
  • 3-way isolation
  • Up to SIL 2 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2441

General specifications
Signal typeUniversal
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA
Power consumption≤ 700 mW
Analog input
Suitable field devices2-wire SMART transmitters, current sources
Signal0/4 ... 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected
Field circuitSL2: 5a(+), 5b(-) (2-wire SMART transmitter)
SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source)
Voltage dropapprox. 4 V (current source)
Control circuitSL1: 8a(+), 7a(-)
Supply voltagemin. 16 V at 20 mA (2-wire SMART transmitter)
Voltage15 ... 30 V
Signal0/4 ... 20 mA , sink mode , working voltage 15 ... 30 V
Ripple20 mV rms
Analog output
Suitable field devicesI/P converters (positioner), on-site-displays
Signal0/4 ... 20 mA
Field circuitSL2: 5a(+), 5b(-)
Load0 ... 650 Ω
Voltage≥ 13 V at 20 mA
Ripple20 mV rms
Control circuitSL1: 8a(+), 7a(-)
Voltage12 ... 30 V
Signal0/4 ... 20 mA
Line fault detection> 100 kΩ at max. 30 V, with field wiring open
Digital input
Field circuitSL2: 5a(+), 1a(-) (NAMUR sensor)
SL2: 5a(+), 5b(-) (dry contact)
Suitable field devicesNAMUR sensors according to IEC/EN 60947-5-6, dry contacts
Signal0.1 ... 9 mA , sink mode
Open loop voltageapprox. 10 V DC , 1 kΩ series resistance
Signal0.1 ... 9 mA
Control circuitSL1: 8a(+), 7a(-)
Voltage13 ... 30 V
Digital output
Field circuitSL2: 5a(+), 5b(-)
Suitable field devicessolenoid valves, acoustic or visual alarms
Drive capability12 V / 40 mA at 300 Ω load
Open loop voltageapprox. 22 V
Current limit45 mA
Internal resistormin. 240 Ω
Control circuitSL1: 8a(+), 7a(-)
Voltage1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
Current1-signal: 0 ... 45 mA, depending on the output load
0-signal: < 0.1 mA, independent of the output load
Power dissipation1.1 W at 24 V, 300 Ω load (digital output)
Transfer characteristics
Deviationat 20 °C (68 °F)
≤ ±20 µA incl. linearity, hysteresis and supply fluctuations at 4 ... 20 mA (analog input, analog output)
≤ ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output)
Influence of ambient temperature< 2 µA/K (0 ... 70 °C (32 ... 158 °F))
< 3 µA/K (-40 ... 0 °C (-40 ... 32 °F))
Switching frequency≤ 500 Hz with 50 % duty cycle (digital input, NAMUR sensor)
≤ 5 Hz (digital input, dry contact)
≤ 20 Hz (digital output)
Frequency rangeHART: bandwidth by 0.5 Vpp signal and/or 1 mApp signal 950 ... 2500 Hz (analog input, analog output)
Settling time≤ 20 ms (analog input, analog output)
≤ 1 ms (digital input, NAMUR sensor)
Reaction time≤ 5 ms , turn-on/turn-off time (digital output)
Galvanic isolation
Control/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
Protection against electrical shockIEC 61010-1:2010
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Observe the temperature range limited by derating, see section derating.
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 1 and 4 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-Type Examination CertificateTÜV 14 ATEX 153522 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
EquipmentSL2: 5a(+), 5b(-)
Voltage Uo25.2 V
Current Io110 mA
Power Po693 mW
EquipmentSL2: 5a(+), 1b(-)
Voltage Ui< 28 V
Current Ii< 115 mA
Voltage Uo7.2 V
Current Io0 mA
Power Po0 mW
EquipmentSL2: 5a(+), 1a(-)
Voltage Uo12.6 V
Current Io13 mA
Power Po41 mW
CertificateTÜV 14 ATEX 153523 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
UL approvalE106378
Control drawing116-0408 (cULus)
IECEx approval
IECEx certificateIECEx TUN 15.0004X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: HiC2441

ManualsLanguageFile TypeFile Size
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Safety ManualENGPDF341 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction manuals
ИнструкцииBULPDF151 KB
Návod k poużitíCZEPDF144 KB
Instruktions manualDANPDF144 KB
Instruction manualENGPDF148 KB
KasutusjuhendESTPDF140 KB
KäyttöohjeFINPDF140 KB
Manuel d'instructionsFRAPDF145 KB
BetriebsanleitungGERPDF151 KB
Οδηγίες χρήσηςGREPDF155 KB
HandleidingHOLPDF145 KB
Instruction manual / BetriebsanleitungHRVPDF143 KB
Használati útmutatóHUNPDF146 KB
Manuale di istruzioniITAPDF143 KB
Lietošanas pamācībaLAVPDF143 KB
Instrukciju vadovasLITPDF144 KB
Instrukcja obsługiPOLPDF147 KB
Manual de instruçõesPORPDF145 KB
Manual de utilizareRONPDF144 KB
Návod na poużitieSLKPDF143 KB
Navodila za uporaboSLVPDF142 KB
Manual de instruccionesSPAPDF145 KB
ManualSWEPDF141 KB
Product information
Product information - Enhancing project performance - THE BARRIERENGPDF351 KB
Produktinformation - Projektperformance steigern - THE BARRIERGERPDF355 KB

Approvals+Certificates: HiC2441

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1863CPDF401 KB
Certificates
Belarus Pattern ApprovalNr. 11708PDF8943 KB
Canada UL cULE106378 cUL (QUZW8)LINK---
Canada UL cULE106378 cUL (QVAJ8)LINK---
EAC NANIO "CCVE" EAC TP TC 012/2011TC RU C-DE.AA87.B.00210PDF1396 KB
Europe TUV Nord ATEX Category 3 GTÜV 14 ATEX 153523 XPDF156 KB
Europe TUV Nord II (1) D I (M1) II (1) GTÜV 14 ATEX 153522 XPDF189 KB
Russia VNIIMSDE.C.34.004.A No.64324/1PDF10397 KB
TUV Nord Ex ec IECEx Certificate of ConformityIECEx TUN 15.0004XLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20190302 - E106378 RepRef 20190227PDF250 KB
USA ULE106378 UL (QVAJ2)LINK---
USA ULE106378 UL (QUZW2)LINK---
Worldwide TUV Nord Functional Safety CertificateCert. No. 44 207 13734004PDF1462 KB
Control drawings
Control Drawing UL / Control Drawing UL   PDF130 KB

Function: HiC2441

This isolated barrier is used for intrinsic safety applications.

The device can transfer the following signals:
- as an analog input: 0/4 mA ... 20 mA
- as an analog output: 0/4 mA ... 20 mA
- as a digital input: signals from NAMUR sensors or
dry contacts
- as a digital output: max. 45 mA

The device requires no configuration and adapts itself automatically to the function of the active input/output of the connected process control system.

The device permits the bi-directional pass-through of the HART communication.

The device is designed primarily for use with universal I/O cards (e. g. Honeywell Universal Process IO).

This device mounts on a HiC Termination Board.