Serviceline Industrial Sensors
Serviceline Explosion Protection

Surge Protection Barrier M-LB-Ex-2142

M-LB-Ex-2142
  • Surge protection barrier for 2 signal lines
  • Nominal voltage 24 V DC
  • Surge protection barrier for non-grounded signal lines
  • Max. surge current (8/20 µs) 20 kA
  • Connection via screw terminals
  • DIN rail mountable
  • Up to SIL 3 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  M-LB-Ex-2142

Product Description
Surge protection barrier for 2 signal lines
General specifications
Number of protected signal lines2
Topologynon-grounded
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Electrical specifications
Connectionprotected area: terminals 4, 5
unprotected area: terminals 2, 3
shielding/grounding: terminal 1 (optional)
Rated current500 mA , restrictions see derating characteristics
Leakage current< 3 µA at 24 V and 25 °C (77 °F) , line-line
Nominal voltage24 V DC
Maximum continuous operating voltage30 V DC
Series resistance≤ 3 Ω per line
Impulse rating1 kV/0.5 kA (category C1)
10 kV/5 kA (category C2)
1 kA (category D1)
Impulse discharge current (10/350 µs)1 kA per line (2x)
Nominal discharge current (8/20 µs)5 kA per line (10x)
Total discharge current (8/20 µs)20 kA (1x) , overstressed fault mode 3 acc. to IEC 61643-21
Voltage protection levelmax. 45 V line-line for nominal discharge current In
max. 1400 V line-earth for nominal discharge current In
Impulse reset time< 500 ms
Insertion loss≤ 3 dB at 0 ... 900 kHz in 100 Ω system
Conformity
Electromagnetic compatibilityEN 61326-3-1:2017
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Surge protective devices for low voltageIEC 61643-21:2000+A1:2008+A2:2012
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
Observe the temperature range limited by derating, see section derating.
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 95 % , without condensation
Mechanical specifications
Degree of protectionIP20 , after mounting of the insulation spacer
Connectionscrew terminals , max. core cross section 1 x 2.5 mm2
MaterialPolyamide (PA)
Massapprox. 32 g
Dimensions6.2 x 72.4 x 93 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateKIWA 19 ATEX 0003 X
MarkingEx-Hexagon II 2(1)G Ex ia [ia Ga] IIC T6...T4 Gb
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Temperature classT6, T5 or T4 , restrictions see derating characteristics
Voltage30 V
Current500 mA , restrictions see derating characteristics
Internal capacitancenegligible
Internal inductance20 µH
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
IECEx approval
IECEx certificateIECEx KIWA 19.0003X
IECEx markingEx ia [ia Ga] IIC T6...T4 Gb
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Designation- insulation spacer M-LB-2800
- terminal block USLKG5

Documents: M-LB-Ex-2142

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF602 KB
ManualENGPDF2037 KB
HandbuchGERPDF2025 KB
Handbuch Funktionale SicherheitGERPDF612 KB
Instruction manuals
ИнструкцииBULPDF145 KB
Návod k poużitíCZEPDF140 KB
Instruktions manualDANPDF139 KB
Instruction manualENGPDF144 KB
KasutusjuhendESTPDF135 KB
KäyttöohjeFINPDF134 KB
Manuel d'instructionsFRAPDF141 KB
BetriebsanleitungGERPDF145 KB
Οδηγίες χρήσηςGREPDF148 KB
HandleidingHOLPDF140 KB
Instruction manual / BetriebsanleitungHRVPDF136 KB
Használati útmutatóHUNPDF140 KB
Manuale di istruzioniITAPDF139 KB
Lietošanas pamācībaLAVPDF138 KB
Instrukciju vadovasLITPDF139 KB
Instrukcja obsługiPOLPDF140 KB
Manual de instruçõesPORPDF140 KB
Manual de utilizareRONPDF139 KB
Návod na poużitieSLKPDF140 KB
Navodila za uporaboSLVPDF137 KB
Manual de instruccionesSPAPDF140 KB
ManualSWEPDF137 KB

CAD+CAE: M-LB-Ex-2142

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS10648 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP3675 KB

Approvals+Certificates: M-LB-Ex-2142

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4287PDF87 KB
Certificates
Europe KIWA I (M1) II 2(1)G ATEX II (1) DKIWA 19 ATEX 0003 XPDF116 KB
Worldwide KIWA IECEx Certificate of ConformityIECEx KIWA 19.0003XLINK---
Worldwide TUV Rheinland Functional Safety Certificate968/FSP 1856.00/19PDF620 KB

Associated Products: M-LB-Ex-2142

Accessories
For surge protection system M-LB-2000, Color black, DIN rail mountablepa
Accessory Zener Barriers, Accessory Surge Protection, For equipotential bonding via the standard railpa

Function: M-LB-Ex-2142

The device limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal loop voltage during the duration of the overvoltage pulse.

The device is used for intrinsic safety applications.

The device is HART transparent.

The device is mounted on a 35 mm DIN mounting rail according to EN 60715.

Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.

Intelligent Surge Protection M-LB-5000

The M-LB-5000 surge protection system offers a combination of diagnostics and modularity within a narrow housing design of only 6.2 mm width. Explore the easiest way to protect plant assets …