Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Switch Amplifier HiC2821

HiC2821
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • Usable as signal splitter (1 input and 2 outputs)
  • Relay contact output
  • Fault relay contact output
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of HiC2821

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA
Power dissipation≤ 500 mW
Power consumption≤ 500 mW
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Output
Connection sidecontrol side
ConnectionSL1: 8a, 7a; 10a, 9a
Output Isignal ; relay
Output IIsignal or error message ; relay
Contact loading50 V DC / 0.5 A
Minimum switch current2 mA / 24 V DC
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Mechanical life107 switching cycles
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency≤ 10 Hz
Galvanic isolation
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Galvanic isolationEN 50178:1997
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-Type Examination CertificateBASEEFA 06 ATEX 0093 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Contact loading50 V DC / 0.5 A
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
CertificatePF 08 CERT 1047 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing16-534FM-12 (cFMus)
UL approval
Control drawing116-0434
IECEx approvalIECEx BAS 06.0026X
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: HiC2821

ManualsLanguageFile TypeFile Size
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction leaflets
Control drawing cULus / Control drawing cULusALLPDF80 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF141 KB
Návod k poużitíCZEPDF0 KB
Instruktions manualDANPDF136 KB
Instruction manualENGPDF141 KB
KasutusjuhendESTPDF0 KB
KäyttöohjeFINPDF131 KB
Manuel d'instructionsFRAPDF138 KB
BetriebsanleitungGERPDF142 KB
Οδηγίες χρήσηςGREPDF0 KB
HandleidingHOLPDF136 KB
Instruction manual / BetriebsanleitungHRVPDF135 KB
Használati útmutatóHUNPDF0 KB
Manuale di istruzioniITAPDF136 KB
Lietošanas pamācībaLAVPDF135 KB
Instrukciju vadovasLITPDF135 KB
Instrukcja obsługiPOLPDF138 KB
Manual de instruçõesPORPDF136 KB
Manual de utilizareRONPDF135 KB
Návod na poużitieSLKPDF136 KB
Navodila za uporaboSLVPDF134 KB
Manual de instruccionesSPAPDF136 KB
ManualSWEPDF132 KB

Approvals+Certificates: HiC2821

Statements of complianceCertificate No.File TypeFile Size
EU- Declaration of conformity / EU- KonformitätserklärungDOC-0927BPDF91 KB
Certificates
Baseefa IECEx Certificate of ConformityIECEx BAS 06.0026XLINK---
Canada FMCoC 3026498CPDF120 KB
Canada UL cULE106378 cUL (QUZW8)LINK---
China NEPSIGYJ17.1285PDF1858 KB
DNV GL MarineA-13966PDF63 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 06 ATEX 0093XPDF1225 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 08 CERT 1047 XPDF212 KB
India CCOEA/P/HQ/MH/104/4012(357998)PDF903 KB
Pepperl+Fuchs Functional Safety AssessmentPF 12 CERT 2161PDF64 KB
Russia Belarus EAC Kazakhstan NANIO "CCVE"TC RU C-IT.GB05.B.00718PDF2731 KB
TUV Rheinland BrazilTÜV 14.0085 XPDF636 KB
USA FMCoC 3026498PDF200 KB
USA ULE106378 UL (QUZW2)LINK---
exida Functional Safety AssessmentP+F 1109-099-C R026 V1R0PDF464 KB
Control drawings
Control Drawing FM / Control Drawing FM   PDF112 KB
Control Drawing UL / Control Drawing UL   PDF92 KB